Parameterization
Page 64 of 72
MSM-USM2G-BA-UK-004
5.5 Reset to factory settings
The fault annunciators can be reset to the factory settings using the keys on the front panel.
To restore the factory settings, please proceed as follows:
1. Press keys 1 and 4 simultaneously for about 2 seconds
2. The signal lamp 1 at the top in the left column lights up orange, the signal
lamp 2 below it lights up red or green and the internal horn is excited briefly.
The "OK" LED above the buttons flashes red-green. The fault annunciator is
now in parameter adjustment mode.
3. By pushing key 3 several times, the second signal lamp in the left column can
be switched over between the colours red and green. The LED colour signals
which action is carried out in the following step:
Red - keep current configuration
Green - Reset to factory settings.
4. In the next step, the selected action is confirmed by pressing button 4..
5. If the action has been selected to "Reset factory setting" (green signal lamp 2),
the fault indicator needs a few seconds to carry out the action, which is concluded with an
alternating green flashing of the indicator lamps "OK", "S1" and "S2". Hence the fault indicator
is in delivery condition.
6. After a voltage reset, the configuration interface of the fault indicator can be called again under
the
IP address 192.168.1.99
.
6 Parameterization via Excel file
In many applications, a part of the required information for parameterization is already available in
Excel-files (e.g. data point lists). In this case it is useful to transfer this information to a template and
import it into the annunciator. EES provides a template that can be filled in and processed with
common procedures. With the Excel file the parameters for the alarm channels, repeat relays and IEC
objects can be imported into the WAP.
All other parameters can then separately be adjusted on the web interface.
The file consists of three different tabs which allow for parameterization of the following features:
EES_Input
- Alarm channels and IEC objects
EES_Relay
- Repeat relays
EES_Collective -
Logic disjunctions for 16 „collective alarms“
If the Excel-file contains parameters for additional slave-devices (within a cascaded annunciator
system), these can only be imported if the respective annunciators have been edified in the
parameterization of the master annunciator before.
The given structure of the Excel file must not be changed. This applies especially for the
designations in the first two rows. For a better overview, columns which are not required
can be deleted from the table. Empty columns will not be processed during the import.
For devices with integrated IT security functionality (options "S" and "P"), the security-
relevant settings (port releases, passwords) are also reset to the delivery status.