PD00D01KNX
– Product Handbook
Eelectron Spa
Via Claudio Monteverdi 6, I-20025 Legnano (MI), Italia
Tel +39 0331.500802 - Fax +39 0331.564826
[email protected] www.eelectron.com
C.F. e P.IVA 11666760159 - Capitale sociale: 800.000,00 interamente versato
Tribunale di Milano 359157-8760-07 - CCIAA Milano 1486549
PD00D01KNXFI00030103.DOCX
16/42
Motion detector / Presence detector
Parameter
In the following paragraphs the parameters for the functional block „Motion detector“ are described.
The configuration for
the functional block „Presence detector“ is performed similar.
Parameter
Setting
Value of locking object after bus voltage recovery
Off(0)
On(1)
as before bus voltage failure
query via bus
This parameter determines what the value of the locking communication object will be after bus voltage recovery.
Locking is active
if locking object = 0
if locking object = 1
This parameter determines how the value of the locking communication object is analyzed.
Locking object acts on
sensor
objects (A-B-C-D)
This parameter defines the behavior of the lock.:
Sensor
: When ‘locked’, the sensor itself is disabled. If the overshoot timer has already started (detector switched on),
the overshoot timer will be continued and after the overshoot time the detector switches off (sends C-D). Retriggering
through the detector is not possible as long the lock is set. Retriggering via the extension object is still possible.
Objects
: When ‘locked’ the output communication objects A-B and C-D of the detector will be controlled. Triggering via
the extension
object is still possible.
Behaviour if lock is enabled
detector switches ON, sends A-B
detector switches OFF, sends C-D
detector sends no telegram
This parameter is visible only when parameter “Lock acts on” is set to “objects (A-B-C-D)“.
detector sends no telegram
: Throughout the entire time that the detector has been ‘locked’, it is still passively
monitoring to detect
motion, but just not sending any of the associated telegrams.
This parameter has the following parameter set:
Behaviour if lock is disabled
detector sends current status A-B or C-D)
detector sends no telegram
detector sends current status (A-B or C-D):
If the lock is disabled the detector sends the current status including
the overshoot time left. This behaviour is used for applications “silent mode”, during locking phase no telegrams will
be sent.
Detector sends no telegrams:
If the lock is disabled no telegram will be sent at all. The device enters normal mode
again only in case of a new presence detection
.
detector switches ON, sends A-B:
When the detector is ‘locked’ telegrams A(B) are sent. However no telegrams will
be sent if the
overshoot timer was active prior to ‘locking’. This mode is useful for “continuous ON” applications.
This parameter has the following parameter set:
Behaviour if lock is disabled
detector switches delay off, sends C-D
detector switches at once off, sends C-D
Detector switches delay off, sends C-D:
The overshoot timer will be restarted after Retriggering via the extension
object is still possible. ‘unlock’. If no motion is detected after ‘unlocking’ the detector sends C(D) after the overshoot
time . If motion is detected after ‘unlocking’ the overshoot time is retriggered.
Detector switches at once off, sends C-D:
Telegrams C(D) are sent at once. After unlocking between A and B, B
will not be sent, but C-D immediately.
detector switches OFF, sends C-D:
when the detector is locked telegrams C(D) are sent only if the overshoot timer
was already active,
otherwise no telegrams are sent. This mode is useful for “continuous OFF” applications. This parameter has the
following parameter
set: