Brightness measuring
Parameter
Parameter
Settings
Measuring method of internal light sensor
indirect (calibration by user)
The internal light sensor can only measure directly. The light level on the desk can be determined indirectly by
recomputing, if the pa-rameter is set accordingly. For this, the detector's brightness measurement function must be
calibrated.
Calibration
via object
with adjustment factor
Calibration is carried out either via an object (no. 27) or via adjustment factor.
Adjustment factor
(x 0.1)
1 - 200,
10
This parameter is visible only if the parameter “Calibration” is set to “with adjustment factor.”
In this case, the light measured by the light sensor is multiplied by 0.1 of the set adjustment factor.
Number of values for calculation of average
1;
2
; 4; 8
The internal light sensor measures every second. For brightness measurement, the mean value can be formed from
several values measured consecutively. The number of values to be used to form the mean value is determined via
the above parameter.
Send brightness value cyclically
no
1 second
5 seconds
10 seconds
30 seconds
1 minute
This parameter determines whether and at what intervals the brightness value determined is sent via the bus.
Send brightness value on change
no
at small change
at medium change
at large change
This parameter determines whether the brightness value is sent automatically and immediately when it changes.