Max. dimming value Master
[1 … 255]
1
– 255,
255
This parameter determines the maximum dimming value of the master.
Min. dimming value Master
[1 … 255]
1
– 255,
1
This parameter determines the minimum dimming value of the master.
Master / slave operation
no
yes
This parameter determines whether the controller runs in master/slave operation or not.
First dim value
[1 … 255]
1
– 255,
128
This
parameter is only visible if the parameter “First dim-value when control starts” is set to “copy from parameter”.
This parameter determines the starting value used by the controller for the control value.
First dim-value when, reading from object fails
[1…255]
1
– 255,
128
This parameter is only visible if the parameter “First dim value when control starts” is set to “query from actuator’s status”.
This parameter determines the starting value used by the controller for the control value if the status query of the dimming actuator
does not return a value within one second.
Slaves
The following parameters are only visible if the parameter “master/slave operation” has been set to “Yes”.
Parameter
Setting
Mode of calculation
calculating via characteristic
calculating via offsets
This parameter determines how the control value for the additional lighting groups is calculated.
calculating via characteristic:
The control values for the additional lighting groups are derived from the main control value by calibration
curves transforming the measured (main) luminance level into a calculated luminance level for the position of each additional
lighting groups. If this setting is selected parameter settings in 3.6.6-a apply.
calculating via offset:
The control values for the additional lighting groups are derived from the main control value by an offset that is
entered for each additional lighting group. If this setting is selected parameter settings in 3.6.6-b apply.
Number of slaves
1
– 4,
4
This parameter determines the number of additional lighting control groups.
Max. dimming value slave 1 [2, 3, 4]
[1 … 255]
1
– 255,
255
This parameter determines the maximum dimming value of the respective additional lighting control group (1…4).
Min. dimming value slave 1 [2, 3, 4]
[1 … 255]
1
– 255,
1
This parameter determines the minimum dimming value of the respective additional lighting control group (1…4).
Slave offset data
The following parameters are only visible if the parameter
“master/slave operation” has been set to “Yes” and the
parameter
“Mode of calculation” has been set to “calculation via offsets”.
Parameter
Setting
Offset for slave 1 to the master dimming value in percent
(-
100…100)
0
(-
100…100)
This parameter determines the offset used to calculate the dimming value for slave 1 from the dimming value of the master.
Note: The limits for the minimum and maximum control values apply.
Offset for slave 2 to the master dimming value in percent
(-
100…100)
0
(-
100…100)
This parameter determines the offset used to calculate the dimming value for slave 2 from the dimming value of the master.
Note: The limits for the minimum and maximum control values apply.
Offset for slave 3 to the master dimming value in percent
(-
100…100)
0
(-
100…100)
This parameter determines the offset used to calculate the dimming value for slave 3 from the dimming value of the master.
Note: The limits for the minimum and maximum control values apply.
Offset for slave 4 to the master dimming value in percent
(-
100…100)
0
(-
100…100)
This parameter determines the offset used to calculate the dimming value for slave 4 from the dimming value of the master.
Note: The limits for the minimum and maximum control values apply.