pag.28
420010399601
MULTICALOR 170.1 -200.1 P AB
EN
1 - Fuse
2 - Termal lock-out lamp
3 - Light-oil working lamp
4 - Gas working lamp
5 - High-low flame selector switch
6 - Main switch I / O
7 - Gas/Light-oil selector switch:
1- Light-oil operation
2- Gas operation
8 - Lockout disable push button
0
1
2
0
1
2
0
0
I
1
2
6
3
5
4
8
7
0
1
2
0
0
1
2
0
DESCRIPTION OF CONTROL PANEL
3
÷
4 mm
5
÷
6 mm
POSITION OF IGNITION ELECTRODES
NOZZLE CLEANING AND REPLACEMENT
Use only the suitable box wrench provided for this operation to remove the
nozzle, taking care to not damage the electrodes. Fit the new nozzle with the
same care.
Note: Always check the position of electrodes after having replaced the
nozzle (see illustration). A wrong position could cause ignition troubles.
WORKING OF THE BURNER WITH LIGHT-OIL FUEL
Once having installed the burner, check the following items:
- The burner power feeding and the main line protection fuses
- The correct length of pipes and that the same are sealed.
- The type of fuel, which must be suitable for burner.
- The connection of boiler’s thermostats and all the safeties.
- The motor rotation direction.
- The correct calibration of the motor’s thermal protection.
When all the above mentioned conditions are checked and accomplished, it is possible to go on
with burner’s tests. Power the burner. The control box feeds the ignition transformer and the burner’s motor at the
same time, which will run a prepurging of the combustion chamber for about 20 sec.
At the end of prepurging, the control box opens solenoid valves and the burner starts. After a safety interval of 5
seconds and a correct ignition, the control box turns off the ignition transformer and, 10 seconds later, sets the motori-
sed air damper to its maximum opening (High flame). In case of faulty ignition, the control box switches the burner
into safety condition within 5 second. In such a case, the manual rearming of the burner shall not take place before 30
seconds have elapsed from the burner’s safety shutdown. In order to obtain an optimal combustion, it is necessary adju-
st the LOW - HIGH flame air flow, according to the instruction given further on. During such a phase, it will be possi-
ble to manually switch between HIGH and LOW flame and viceversa, through the High/Low flame switch. At the end
of the adjusting phase, leave the switch in position AUTO.
0
1
2
0 − STOP
1 − GASOLIO
2 − GAS
LIGHT-OIL