![Eco Power Equipment IAQH Series Скачать руководство пользователя страница 61](http://html1.mh-extra.com/html/eco-power-equipment/iaqh-series/iaqh-series_installation-and-user-instructions-manual_3999244061.webp)
IAQH-1000 Manual
8. Follow the same process and place the control loop back into AUTO mode
9. WARNING: This overrides the control loop and can cause the heater to overheat and
shutdown, and should only be used by trained personnel for the purpose of
commissioning the unit or advanced troubleshooting — the system will automatically
switch into manual mode at 0%. The control loop MUST be turned back to auto for
proper operation
8.1.4
Starting/Stopping the product’s operation
The system is designed to manage all aspects of the heater operation, see above information for
details on operations.
NOTE: It is critical that on shut down of the unit that time is allowed for the cool down cycle of
the heat exchanger. Without proper cooling of the heat exchanger expansion and contraction of
the heat exchanger can occur at uneven levels causing distortion, heat exchanger damage, even
complete heat exchanger failure.
To Properly turn off the unit
1. Press the HEAT ON/OFF button to OFF
2. Ensure Vent ON/OFF is off
3. Wait until fans turn off
4. The unit can now safely be disconnected from power
61
Содержание IAQH Series
Страница 2: ...2 Eco Power Equipment Ltd ...
Страница 21: ...IAQH 1000 Manual 21 ...
Страница 22: ...IAQH 1000 Manual 22 ...
Страница 50: ...IAQH 1000 Manual Gas Connection and Burner Setup FIgure GT1 50 ...
Страница 56: ...IAQH 1000 Manual Figure RTC Figure Midco 1 56 ...
Страница 57: ...IAQH 1000 Manual Figure RTC 2 57 ...
Страница 80: ...IAQH 1000 Manual Combustion Analysis O2 CO CO2 Efficiency Stack Temperature Ambient Temperature Excess Air 80 ...