![Eco Power Equipment IAQH Series Скачать руководство пользователя страница 59](http://html1.mh-extra.com/html/eco-power-equipment/iaqh-series/iaqh-series_installation-and-user-instructions-manual_3999244059.webp)
IAQH-1000 Manual
OPERATION/USE
d.
How to Use the Machinery
The installation shall conform with local codes, or, in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the National Gas and Propane Installation
Code, CSA B149.1
i.
Heating Mode
1
Turn on the main power disconnect switch, if the ambient temperature is less than 5 °C or
41 °F, wait 10–15 minutes for the control panel heater to bring control system up to
operating temperature
2
Turn on the controls ON/OFF switch to the ON position
3
Wait for unit to power up display — this typically takes 30–60 seconds; note in extreme cold
weather conditions we recommend you plug in the power and turn on the main power
disconnect switch and leave it on for 10–15 minutes to allow the control internal panel
heater to come up to temperature and heat all electrical components before turning on the
controls ON/OFF switch
4
Setup and deploy remote temperature and humidity sensor probe inside area being
controlled; please note: multiple cables can be connected together if required for extra
distance, ensure to twist connections together well to prevent moisture from entering the
connection, the maximum length is 250 ft or 76 m
5
Set the desired temperature for the space on HX control loop SP (Setpoint) to your desired
space temperature
6
Press HEAT ON/OFF button
7
The fan system will automatically turn on once heat in the exchanger area increases, this is
to allow for the system to preheat before turning on fans so that only treated air is sent to
the heating area
8
The unit will now automatically modulate the heat output to reach the temperature set
point (SP) as programmed by the user. The fans on this system never shut off in this
operation mode, when the space reaches set point temperature, or as the call for additional
heat decreases the unit will automatically decrease heat output temperature according to
the maximum output temperature of 158°F or 70 °C. The fans never turn off, however, they
do modulate with the demand for heat as the power level demand for the heater drops, the
59
Содержание IAQH Series
Страница 2: ...2 Eco Power Equipment Ltd ...
Страница 21: ...IAQH 1000 Manual 21 ...
Страница 22: ...IAQH 1000 Manual 22 ...
Страница 50: ...IAQH 1000 Manual Gas Connection and Burner Setup FIgure GT1 50 ...
Страница 56: ...IAQH 1000 Manual Figure RTC Figure Midco 1 56 ...
Страница 57: ...IAQH 1000 Manual Figure RTC 2 57 ...
Страница 80: ...IAQH 1000 Manual Combustion Analysis O2 CO CO2 Efficiency Stack Temperature Ambient Temperature Excess Air 80 ...