IAQH-1000 Manual
12. Combustion Air
a. The burner requires combustion air and ventilation air for reliable operation.
Assure that the Building and/or combustion air openings comply with National
Fuel Gas Code NFPA 54/CSA B149. For appliance/burner units in confined
spaces, the room must have an air opening near the top of the room plus one
near the floor, each with a free area at least one square inch per 1000 Btu/hr
input of all fuel burning equipment in the room. For other conditions, refer to
NFPA 31 or CSA B1139-M91.
b. If there is a risk of the space being under negative pressure or of exhaust fans or
other devices depleting available air for combustion and ventilation, the
appliance/burner should be installed in an isolated room provided with outside
combustion air.
Installation Checklist:
1.
All permits have been acquired based on installation jurisdiction
2.
Gas Supply pressure is within specification, line sizing is correct and the
regulators are appropriately rated for the BTU rating of the appliance as found
on the nameplate of the unit
3.
Fuel supply is a commercial grade, HD5 Propane or 1075 BTU/ft³ NG
4.
All unions, fittings, and connections are free from leaks and leak tested
5.
Chimney vent is connected, unobstructed, and meets clearance requirements
6.
Chimney vent is free of leaks & cracks, and meets layout requirements in 4.2.3
7.
Duct connections are unobstructed, with minimal bends and restrictions
8.
Gastrain supports are fully secured and the gas train is stable
9.
Intake vent is unobstructed, with no ice or debris present
10.
Heater is level and does not slope any more than 5 degrees in any direction
11.
Combustion Air Supply meets code requirement
12.
Electrical connections are in accordance with local authority having
jurisdiction and placed in a way to reduce or eliminate trip hazards or risk of
damage
13.
Voltage is within the range specified on the rating plate of the appliance
47
Содержание IAQH Series
Страница 2: ...2 Eco Power Equipment Ltd ...
Страница 21: ...IAQH 1000 Manual 21 ...
Страница 22: ...IAQH 1000 Manual 22 ...
Страница 50: ...IAQH 1000 Manual Gas Connection and Burner Setup FIgure GT1 50 ...
Страница 56: ...IAQH 1000 Manual Figure RTC Figure Midco 1 56 ...
Страница 57: ...IAQH 1000 Manual Figure RTC 2 57 ...
Страница 80: ...IAQH 1000 Manual Combustion Analysis O2 CO CO2 Efficiency Stack Temperature Ambient Temperature Excess Air 80 ...