![Eco Power Equipment IAQH Series Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/eco-power-equipment/iaqh-series/iaqh-series_installation-and-user-instructions-manual_3999244015.webp)
IAQH-1000 Manual
c.
Technical Data
Parameter
Unit
Device name
IAQH Indirect Fired Heater
Designation
IAQH-1000
Type
Indirect Fired
Technical life span
10,000+ Hours
Maximum Input BTU
1,000,000 BTU/HR / 293 kW
Energy consumption
Natural Gas: 1.0551 GJ/hour, 985 ft
³/hour
, 27.89 m
³
/
hour
Liquid Propane: 41.32 LPH / 10.92 GPH
Gas Types
Natural Gas: (Pipeline Quality) (1075 BTH/ft
³
) (40.1
MJ/m
³
)
Liquid Propane: (HD-5 Spec) (2500 BTU/ft
³
) (93.1 MJ/m
³
)
Weight
2200 lbs / 1225 kg
Input Gas Pressure
10 inH20 / 24.8 mbar / 0.36 psi
Voltage
208/240 Three Phase
Recommended Circuit Size
30 Amps
Full Load Amps
24 Amps
Frequency
60 Hertz
SCCR Rating
10 kA
Max Heater Efficiency
82%
Blower Type
Backwards Inclined EC Type Blower
Heater Air CFM Rating
10 000 CFM
Compliance
ANSI Z83.7 / CSA 2.14 / CSA C22.2 No. 3
Product Certification Agency
Intertek cETLus
Full Load Operating Sound Level
58 dBa @ 7 Meters (with ducting connected to building)
Installation Details
For installation above 2000 ft (610 m), see the
“high-altitude rating plate."
Unit is automatically de-rated in high elevation conditions.
15
Содержание IAQH Series
Страница 2: ...2 Eco Power Equipment Ltd ...
Страница 21: ...IAQH 1000 Manual 21 ...
Страница 22: ...IAQH 1000 Manual 22 ...
Страница 50: ...IAQH 1000 Manual Gas Connection and Burner Setup FIgure GT1 50 ...
Страница 56: ...IAQH 1000 Manual Figure RTC Figure Midco 1 56 ...
Страница 57: ...IAQH 1000 Manual Figure RTC 2 57 ...
Страница 80: ...IAQH 1000 Manual Combustion Analysis O2 CO CO2 Efficiency Stack Temperature Ambient Temperature Excess Air 80 ...