3.2 GLT x010 models
The GLT 3010 and the GLT 5010 only differ in their
. The main features are:
Compared to the GLT 3010, the GLT 5010 can embed the GLT channel configuration "glt.cfg" (data point
description) in the user application running on it. Compared to the GLT 3010, there is
no longer
a separate
"glt.cfg" file that has to be manually imported into the system centre. In addition, the Virtus 5 can then manage
more
per GLT 5010.
The current procedure for importing the GLT-3010 configuration is to import it into the system centre via
LDSWin. This currently results in the following disadvantages:
The GLT configuration "glt.cfg" contains all data points about all GLT 3010 controllers that are in the system.
The GLT 3010 controllers can also be located in different maintenance groups, e.g. in the "building
management system" group and in the "refrigeration" group for heat recovery. In the case of any change, it
must be ensured that the corresponding Signal Lists for all maintenance groups have been merged before
importing.
In the case of any change in the CODESYS project of the GLT 3010 and the possibly resulting changes in
the data points, it must currently be ensured that the corresponding GLT configuration is also available in
the system centre or is imported subsequently. If this is not the case, then incorrect or implausible actual
and setpoint values are displayed in LDSWin because the GLT configuration does not match the CODESYS
project of the GLT 3010.
The new concept envisages that the GLT channel configuration is embedded in the CODESYS project of the
controller.
The concept has been implemented in the Virtus 5 series system centre and GLT 5010, for more details about
these aspects, see chapter
. The hardware of the GLT 3010 controller is not affected, i.e. a GLT
3010 controller can be transformed into a GLT 5010 controller via a firmware upgrade. The following are
created from the EXCEL Signal List with the GLT channels for a DDC using the
the files of the PLC code for the CODESYS project and
file of the GLT channel configuration (glt.cfg)
The GLT channel configuration is then integrated into the CODESYS project and is stored in the controller after
import. The GLT channel configuration is then transmitted via CAN bus to the system centre and is stored there.
When a connection is established, LDSWin retrieves all available GLT configurations and displays them in the