Firmware: V2.18 / V--
26.10.2022
69/119
9.1 DIN rail mounting
The base module and the SIOX extension modules are snapped onto a DIN rail using two claws on the rear
side, for details see chapter
Specified mounting position
The base module must be mounted as follows:
For details about protection rating and dimensions, see chapter
Technical Data GLT x010 / SIOX
ATTENTION
The controller may only be operated when mounted on a DIN rail as a built-in regulating and control
device (EN 60730) and can be mounted in a row without spacing. The power loss of the controller is 24
W and 3.1 W per SIOX. The natural convection of the circulating air with free air exchange is sufficient
for the operation of the controller to prevent overheating. A sufficiently large air inlet (min. 30 mm)
under the device and an unobstructed air outlet above it
must
always be ensured. If this cannot be
guaranteed, forced ventilation is required!
All supply lines from and to the device (with the exception of the 230 V power supply and signal lines)
must be shielded! This particularly applies to the analogue inputs and outputs as well as to the CAN
bus and Modbus cabling; see operating manual
Basics and General Safety and Connection
". These must also be installed with sufficient clearance from live cables. As a general rule,
care should be taken to ensure that signal cables and cables carrying mains voltage are routed in
separate cable channels