Firmware: V2.18 / V--
26.10.2022
80/119
9.3.4 Configuration of the analogue inputs and outputs
The analogue inputs and outputs can be configured using jumpers on the
bottom
circuit board of the controller.
The analogue inputs and outputs are configured at the factory as follows:
1..6
7
0..10 V
4..20 mA
(AOUT)
1..4
0..10 V
DANGER
Warning about dangerous electrical voltage! Danger to life - Danger of electric shock!
Before opening the case, it is essential to disconnect the device from the power supply! All plug
connectors may only be inserted and removed when the power supply is disconnected. For details
about opening the case, see chapter
.
Reconfiguration of the analogue inputs and outputs is
only
necessary if settings different from the
delivered condition have to be made, e.g. if analogue signals with 4..20 mA signal existing in the
system should be used. A reconfiguration or any opening of the controller must only be performed by
trained personnel or at the factory by the manufacturer. Incorrect handling can result in damage and
impairment of the controller functions!
After opening, the device
must
be subjected to an
insulation test
!
Practical tip:
For better interference immunity, the analogue inputs should be configured for 4..20 mA
current for long cable lengths.