Firmware: V2.18 / V--
26.10.2022
84/119
4. Remove connector (1) and remove bottom circuit board (2).
6. Pick up the new battery with a cloth and push it into the battery holder.
7. Assembly is performed in reverse order. Reconnect all connectors.
8. Supply the controller with power again. The application works again.
9. In the case of unchanged configuration, the controller will be automatically detected again via the CAN bus.
Date, time and automatic switching between summer / winter time are performed automatically via the central
time synchronisation by the higher level controller.
(Error) messages are output during restart of the controller. These must be checked / acknowledged in the
higher level controller (
system centre / store computer / operator terminal
It is recommended to perform a first start after the battery replacement!
5. Pull the battery (1) upwards out of the battery holder and dispose of correctly.
ATTENTION
The device may contain a lithium battery (for details, see chapter Electrical Data) that
must be disposed of separately! Please inform yourself about the local regulations for
the separate disposal of electrical and electronic products and batteries.
•
•
ATTENTION
Do
not
handle the new battery with metal pliers as the battery can be destroyed by the resulting short
circuit:
wipe with a clean and dry cloth.
do
not
hold on the edge contact areas.
Warning about dangerous electrical voltage! Danger of electric shock!
A voltage of 230 V AC can
be present on some connectors.