5.3.4 Number of SIOX extension modules
The number of SIOX extension modules connected to the controller is defined in the controller configuration.
The minimum number is 0 (i.e. no SIOX) and the maximum number is 3:
Base module GLT x010 in full expansion with max. 3 SIOX extension modules, for details, see chapter
The number of SIOX extension modules is configured in the "Module parameters" tab (see also
). The selection can be found as follows:
Controller configuration → GLT3010_V2 → System IO →
System state [FIX]
. There, select "Module parameters" on the right-hand side and enter the desired number of
SIOX extension modules in the "Value" column. The factory default value is 3, see column "Default":
If fewer SIOX extension modules than entered under "Value" are connected to the base module (or
one of them fails during operation), the system alarm "Failure ext. SIOX x" is triggered.