Application of AL 300
9
Version 3-1 05. Dezember 2019
2.2
Circuit points
Connectivity for the AL 300 Operator Terminal is as follows (for details see chapter Pin and Terminal Assign
ments):
Inputs/outputs:
S
2 x digital inputs 230 V AC e.g. for monitoring of external alarms
S
3 x relay outputs 230 V AC, floating output:
- 2 x alarm contacts (PRIO1/2) e.g. for connection of a telephone dialling device
- 1 x audible signalling unit (HORN)
S
1 front button with external wiring option
Interfaces:
S
CAN bus interface for interconnection of all LDS components (CI 4x00 System Centre, CI 3000 Store
Computer, other AL 300 Operator Terminal types, UA 300-/UA 400 Family case/coldroom controllers and
VS 3010, VS 3010 BS, VS 3010 CT, Vs 3010 WP, FS 3010 or VS 300 Pack Controllers, Receiver Modules
WR 300 / WR 400)
S
RS232 port for special functions (no function, no connection to LDSWin is possible)
2.3
Compatibility with other LDS components
Version 5.06
Functional adaptation to the CI 4x00 System Centre with Version 6.0.0 or higher
Version 4.10
When a CI 3000 Store Computer of Version 4.24 or higher is connected to the LDS System, the AL 300 Opera
tor Terminals used must also be Version 4.10 or higher.
Version 4.08
When a CI 3000 Store Computer of Version 4.19 or higher is connected to the LDS System, the AL 300 Opera
tor Terminals used must also be Version 4.08 or higher.
Содержание AL 300 S
Страница 21: ...Function of AL 300 16 Version 3 1 05 Dezember 2019 Notice ...
Страница 31: ...Pin and Terminal Assignments of AL 300 26 Version 3 1 05 Dezember 2019 Notice ...
Страница 51: ...Decommissioning and disposal 46 Version 3 1 05 Dezember 2019 Notice ...
Страница 59: ...Specifications of AL 300 54 Version 3 1 05 Dezember 2019 Notice ...
Страница 61: ...Order numbers and accessories of AL 300 56 Version 3 1 05 Dezember 2019 Notice ...