Function of AL 300
11
Version 3-1 05. Dezember 2019
3
Function of AL 300
3.1
Messages and alarms
Use in the E*LDS system
The AL 300 Operator Terminal, in addition to the CI 4x00 System Centre and the CI 3000 / CI 3100 Store Com
puter, is the central collection point for messages of all E*LDS components that are listed in an alarm list and
displayed to the operator - see menu 1 "Alarms". The alarm log can store 100 entries. When it is full, the next
new message overwrites the oldest entry. Detailed information on the alarm and message texts is provided in
chapter 8 Alarms and Messages.
Messages generated by the E*LDS components are transmitted to the AL 300 Operator Terminal(s) via the
CAN bus with one of the following priorities:
--
No message is generated, no alerting
0, 10, 20,...90
Message - only entry in the message list
1, 11, 21,...91
High priority alarm - entry in the alarm and message list, activation of the alarm relay PRIO1
(e.g. in the event of potential damage to goods)
2, 12, 22,...92
High priority alarm - entry in the alarm and message list, activation of the alarm relay PRIO2
(e.g. in the event of faults which can be rectified by customer services on the following day)
3, 13, 23,...93
Low priority alarm - Alarm entry in the message and alarm list
4, 14, 24,...94
5, 15, 25,…95
6, 16, 26,…96
7, 17, 27,…97
8, 18, 28,...98
9, 19, 29,...99
Low priority alarm - Only for local alarm signal, no modem,
can be configured to operate the AUX relay
Messages of Priority 0 are ignored by the AL 300 and are not displayed.
Exception
: Messages gen
erated by the AL 300 Operator Terminal itself!If available in the E*LDS system, the display is only
made in the message list of the system centre / store computer. Messages with the priorities X1 and
X2 are designated with "Alarm" below.
Alarms shown in the alarm log can be cancelled and deleted. Each new alarm logged in the alarm log sounds
the audible alarm devices (internal buzzer or external horn). These can be cancelled by pressing the
ALARM
RESET
key:
PRIO 1
PRIO 2
ALARM
RESET
ZNR:
51203
67
530
Содержание AL 300 S
Страница 21: ...Function of AL 300 16 Version 3 1 05 Dezember 2019 Notice ...
Страница 31: ...Pin and Terminal Assignments of AL 300 26 Version 3 1 05 Dezember 2019 Notice ...
Страница 51: ...Decommissioning and disposal 46 Version 3 1 05 Dezember 2019 Notice ...
Страница 59: ...Specifications of AL 300 54 Version 3 1 05 Dezember 2019 Notice ...
Страница 61: ...Order numbers and accessories of AL 300 56 Version 3 1 05 Dezember 2019 Notice ...