background image

8

Normal  Operating  Mode  - 

number  of  long  blinks  indicates  the  linked  device  type 

followed by short blinks counting the number of devices linked.

Description

Learn LED

Power LED

Factory Default

OFF

ON Solid

with linked switch(es)

OFF

1 long blink

 followed by short blinks 

counting switches repeatedly

with linked occupancy sensor(s)

OFF

2 long blinks

 followed by short blinks 

counting sensors repeatedly

with linked photo sensor(s)

OFF

3 long blinks

 followed by short blinks 

counting sensors repeatedly

with central command

OFF

4 long blinks 

followed by short blinks 

counting sensors repeatedly

Manually Configure Dimming Mode

The  dimming  mode  for  the  ER6CD-AU-120  Phase  Adaptive  Dimmer  is  detected 

automatically by default. The dimming mode for the ER6CD-AU-277 is reverse phase by 

default. At the device, you can change the dimming mode manually, entering forward 

phase, reverse phase, or automatic phase dimming.

1. Simultaneously, press and hold the “Learn” and “Clear” buttons for five seconds, 

then release. The CLR/LRN and Status LEDs will begin to flash.

The LEDS indicate which dimming mode is active.

•  Both Green: Forward Phase dimming

•  Both Red: Reverse Phase dimming

•  If the dimmer is in Automatic dimming mode, the Status LED will flash amber, and 

the CLR/LRN LED will indicate the current mode with specific LED colors. (red is 

Reverse Phase dimming mode and green is Forward Phase dimming mode).

2. To change the current mode, press and hold the “Learn” and “Clear” buttons until 

the LEDs change to the desired dimming mode according to the LEDs state.

Note: The device will return to normal operation, exiting the dimming mode menu, 10 

seconds after the last interaction.

Configuring the Controller

There are a few methods of configuring parameters in the controller. Simple Tap is a quick 

method of changing a parameters setting, one at a time. For accessing the complete set 

of configuration parameters, use the Smart Click process on the following pages.
There are three methods of configuring parameters in the controller. 

1.   Simple Tap

2.   Smart Click

3.   Garibaldi Commissioning Software (not covered in this guide)

Simple Tap Instructions 

Simple Tap uses the switches and sensors that are linked to the controller to set the 

associated  configuration  parameters.  You  must  be  able  to  access  the  sensors  teach 

button and switches to perform the Simple Tap process. 
If the sensor is linked to multiple controllers and you do not want to make changes to all, 

turn the controllers relay off (lights off) to ignore the Simple Tap changes.
Simple Tap allows you to:

•  Enable or disable the motion sensor Auto-ON feature

Содержание ER6CD

Страница 1: ...trols 120V electronic low voltage transformer loads Neither of these controllers can accommodate magnetic or step down transformer loads These controllers have a single channel dimming output and uses...

Страница 2: ...essed while the lights are on and the timer is counting down an additional period of time is added to the timer total Example if the timer setting is 1 hour and the user presses the switch ON twice th...

Страница 3: ...t specification item details that a certain value of light must be measured on a desktop The dimming light fixture providing light to the desktop is controlled The light sensor is located over the des...

Страница 4: ...ange confirmation feature to provide visual feedback of a linked sensors signal strength for optimal sensor placement To evaluate the radio signal strength the sensor must be also support the test and...

Страница 5: ...isrupt transmissions Fire doors elevator shafts stairwells storage areas and any large metal objects can create radio shadows and disrupt wireless transmissions It is recommended that switches and sen...

Страница 6: ...off the power to the lighting circuit 2 Remove the face plates and other hardware from the junction box gaining access to the high voltage wiring 3 The dimmer mounts to the exterior of the junction b...

Страница 7: ...ton marked LEARN for a half second In link mode the LEARN LED will stay ON and the POWER LED will toggle every 2 second 2 Using the switch that will be linked to the controller press the wall switch O...

Страница 8: ...mming mode the Status LED will flash amber and the CLR LRN LED will indicate the current mode with specific LED colors red is Reverse Phase dimming mode and green is Forward Phase dimming mode 2 To ch...

Страница 9: ...taps 10 min 3 blinks 6 taps 15 min 4 blinks 7 taps 20 min 5 blinks 8 taps 25 min 6 blinks for demonstration purposes only 2 After the controller has completed responding to the change press the sensor...

Страница 10: ...ge 2 Open Loop The lighting set point can be set to an absolute value useful in open loop sensor applications The absolute value selected becomes the maximum dimming set point 1 With the light on tap...

Страница 11: ...he light is dimming down up twice Press ON for three seconds 2 Click the switch ON 5 times to clear the switch click ON 5 times again to clear ALL switches and sensors and reset the controller to defa...

Страница 12: ...crease the timeout in 5 minute increments 4 To continue with configuration press ON for 3 seconds the light will resume dimming down up five times To exit Smart Click press OFF for 5 seconds Light Tim...

Страница 13: ...es past day lighting set point The lights will turn ON upon the next motion detected by the occupancy sensor When set for daylight harvesting operation the set point is used with a photo sensor light...

Страница 14: ...wn up nine times 2 Press ON for 3 seconds Default setting is 100 Adjust the maximum light level to the brightness level desired by clicking ON to increase and OFF to decrease in 2 increments 3 To cont...

Страница 15: ...Minimum Dimming Output enabled Motion sensor Time out 15 minutes Switch Time out no time out Auto ON Time out enabled with no linked switch disabled with linked rocker switch Light ON Set point 60 of...

Страница 16: ...rmful interference and ii this device must accept any interference received including interference that may cause undesired operation IC RSS 210 Contains IC 5713A STM300U echoflex Powered by ETC Echof...

Отзывы: