background image

11

Linking the First Switch

1. Press the Clear button until the green Learn led blinks ON, approximately 6 

seconds.

2. With the controller cleared or in the factory default state, click the wireless switch 

ON three times, OFF three times and ON three times quickly within 5 seconds. 

Using this method of linking a switch will only work on the first wireless switch. Use the 

learn button or Smart Click to link additional switches.

Entering Smart Click Configuration Mode

It is important to have feedback (attached light) from the controller during configuration. 

The switch used to configure a controller using Smart Click should only be linked to the 

controller you’re configuring. Add an additional switch if necessary.

Entering Smart Click Configuration Mode

1. Using a linked switch (see above), turn the light OFF. 

2.  Click and hold the switch OFF until the light turns on, approximately 10 seconds.

3. Press ON until the light blinks, about 5 seconds. The light will repeatedly blink once 

every 5 seconds.

Level 1 - Linking an additional switch or sensor

1.   Enter Smart Click configuration mode and with the light blinking once, press 

ON for 3 seconds. The light will begin dimming down + up every second.

2.   Add additional wireless switches by clicking ON 3 times quickly. Add sensors 

by pressing the TEACH button on the sensor.

3.   To continue with configuration, press the switch ON for 3 seconds, the light 

will resume dimming once. To exit Smart Click press OFF for 5 seconds.

Level 2 - Clear switches or sensors (restore defaults)

1. 

Enter 

Smart Click configuration mode

 and click the switch ON or OFF until the light 

is dimming down + up twice. Press ON for three seconds.

2. Click the switch ON 5 times to clear the switch, click ON 5 times again to clear ALL 

switches and

 

sensors and reset the controller to defaults.

3. Press OFF for 5 seconds to complete clearing.

Level  3  -  Repeater  Function  - 

repeats  any  telegram  within  range.  Telegrams  can  be 

repeated  once  or  twice  (single  or  dual  hop).  The  repeater  function  can  be  enabled/

disabled by accessing the controller buttons. 

1. Press the Clear button and hold, then quickly press the Learn button; once to 

disable, twice to enable single hop and three times to enable dual hop repeating. 

2. The learn LED will blink the corresponding value of the button press.

3. Release the Clear button. 

Use Smart Click to enable repeating mode. Enter 

Smart Click configuration mode

 and click 

the switch ON or OFF until the light is dimming down + up three times.

1. Press ON for 3 seconds. If the repeater function is enabled the light will turn ON, if 

disabled the light will be OFF.

2. Click ON to activate this function, OFF to deactivate.

3. To continue with configuration, press ON for 3 seconds, the light will resume 

dimming down + up three times. To exit Smart Click press OFF for 5 seconds.

Level  4  -  Status  Telegram  -

  the  controller  can  broadcast  a  status  telegram  per  EEP: 

A5-11-01. The telegram will broadcast every 100 seconds. Refer to the table on page 

15 for a detailed explanation of the telegram. If the controller has a wired occupancy 

sensor connected to the low voltage input, this sensor status can be shared with other 

controllers. The controller must be first linked with the receiving controllers.
Enabling the status telegram activates the shared occupancy feature and also sends the 

learn command to the other controllers for linking. The status telegram can be enabled/

Содержание ER6CD

Страница 1: ...trols 120V electronic low voltage transformer loads Neither of these controllers can accommodate magnetic or step down transformer loads These controllers have a single channel dimming output and uses...

Страница 2: ...essed while the lights are on and the timer is counting down an additional period of time is added to the timer total Example if the timer setting is 1 hour and the user presses the switch ON twice th...

Страница 3: ...t specification item details that a certain value of light must be measured on a desktop The dimming light fixture providing light to the desktop is controlled The light sensor is located over the des...

Страница 4: ...ange confirmation feature to provide visual feedback of a linked sensors signal strength for optimal sensor placement To evaluate the radio signal strength the sensor must be also support the test and...

Страница 5: ...isrupt transmissions Fire doors elevator shafts stairwells storage areas and any large metal objects can create radio shadows and disrupt wireless transmissions It is recommended that switches and sen...

Страница 6: ...off the power to the lighting circuit 2 Remove the face plates and other hardware from the junction box gaining access to the high voltage wiring 3 The dimmer mounts to the exterior of the junction b...

Страница 7: ...ton marked LEARN for a half second In link mode the LEARN LED will stay ON and the POWER LED will toggle every 2 second 2 Using the switch that will be linked to the controller press the wall switch O...

Страница 8: ...mming mode the Status LED will flash amber and the CLR LRN LED will indicate the current mode with specific LED colors red is Reverse Phase dimming mode and green is Forward Phase dimming mode 2 To ch...

Страница 9: ...taps 10 min 3 blinks 6 taps 15 min 4 blinks 7 taps 20 min 5 blinks 8 taps 25 min 6 blinks for demonstration purposes only 2 After the controller has completed responding to the change press the sensor...

Страница 10: ...ge 2 Open Loop The lighting set point can be set to an absolute value useful in open loop sensor applications The absolute value selected becomes the maximum dimming set point 1 With the light on tap...

Страница 11: ...he light is dimming down up twice Press ON for three seconds 2 Click the switch ON 5 times to clear the switch click ON 5 times again to clear ALL switches and sensors and reset the controller to defa...

Страница 12: ...crease the timeout in 5 minute increments 4 To continue with configuration press ON for 3 seconds the light will resume dimming down up five times To exit Smart Click press OFF for 5 seconds Light Tim...

Страница 13: ...es past day lighting set point The lights will turn ON upon the next motion detected by the occupancy sensor When set for daylight harvesting operation the set point is used with a photo sensor light...

Страница 14: ...wn up nine times 2 Press ON for 3 seconds Default setting is 100 Adjust the maximum light level to the brightness level desired by clicking ON to increase and OFF to decrease in 2 increments 3 To cont...

Страница 15: ...Minimum Dimming Output enabled Motion sensor Time out 15 minutes Switch Time out no time out Auto ON Time out enabled with no linked switch disabled with linked rocker switch Light ON Set point 60 of...

Страница 16: ...rmful interference and ii this device must accept any interference received including interference that may cause undesired operation IC RSS 210 Contains IC 5713A STM300U echoflex Powered by ETC Echof...

Отзывы: