4

Setting the set point is covered later in this document under “Configuring the Controller”. 

The  daylight  harvesting  application  can  override  the  Auto-ON  feature  of  occupancy 

sensors if the light level is sufficient and calls for the lights to be off. 
The daylight harvesting application can be overridden by a manual wall switch when the 

light is dimmed to off by clicking the switch on. If the light level remains above the Light-

OFF-Set point, the controller will turn the light off again after 250 seconds. 
The daylight harvesting application does not affect the operation of the wall switch or 

motion sensor when the light is on. If the light is on, either the switch or motion sensor 

can override the light off.
See the section on Occupancy Based Lighting Application - Photo Inhibit for alternative 
functionality.

Radio Range Confirmation

The  “F  series”  controllers  includes  patent  pending  technology  that  works  with  all 

Echoflex  sensors  equipped  with  the  range  confirmation  feature  to  provide  visual 

feedback of a linked sensors signal strength for optimal sensor placement.
To evaluate the radio signal strength, the sensor must be also support the test and be 

linked to the controller. Check the sensors documentation to find out if it supports radio 

range confirmation testing. Do not have any repeaters in the controllers vicinity enabled 

during the test.
The range confirmation test is invoked at the sensor and sends unique telegrams to the 

controller. The controller will evaluate the signal strength from the sensor and send back 

a unique telegram containing the strongest signal value received. This value is displayed 

at the sensor using color LEDs. 
Consult the sensor installation guide for more details.

Specifications

Ambient Environment

For indoor use only.

•  United States only: 32°F to 122°F (0-50 °C)operating temperatures in 5-95% non-

condensing humidity.

•  Canada only: 0°C to 40°C (32-104 °F) operating temperatures in 5-95% non-

condensing humidity.

Electrical Specification

Two models are available including:

•  120 VAC, +/- 10% at 50/60 Hz,maximum load 600 Watts (5A)

•  277 VAC, +/- 10% at 50/60 Hz, maximum load 600 Watts (2.17A)

Содержание ER6CD

Страница 1: ...trols 120V electronic low voltage transformer loads Neither of these controllers can accommodate magnetic or step down transformer loads These controllers have a single channel dimming output and uses...

Страница 2: ...essed while the lights are on and the timer is counting down an additional period of time is added to the timer total Example if the timer setting is 1 hour and the user presses the switch ON twice th...

Страница 3: ...t specification item details that a certain value of light must be measured on a desktop The dimming light fixture providing light to the desktop is controlled The light sensor is located over the des...

Страница 4: ...ange confirmation feature to provide visual feedback of a linked sensors signal strength for optimal sensor placement To evaluate the radio signal strength the sensor must be also support the test and...

Страница 5: ...isrupt transmissions Fire doors elevator shafts stairwells storage areas and any large metal objects can create radio shadows and disrupt wireless transmissions It is recommended that switches and sen...

Страница 6: ...off the power to the lighting circuit 2 Remove the face plates and other hardware from the junction box gaining access to the high voltage wiring 3 The dimmer mounts to the exterior of the junction b...

Страница 7: ...ton marked LEARN for a half second In link mode the LEARN LED will stay ON and the POWER LED will toggle every 2 second 2 Using the switch that will be linked to the controller press the wall switch O...

Страница 8: ...mming mode the Status LED will flash amber and the CLR LRN LED will indicate the current mode with specific LED colors red is Reverse Phase dimming mode and green is Forward Phase dimming mode 2 To ch...

Страница 9: ...taps 10 min 3 blinks 6 taps 15 min 4 blinks 7 taps 20 min 5 blinks 8 taps 25 min 6 blinks for demonstration purposes only 2 After the controller has completed responding to the change press the sensor...

Страница 10: ...ge 2 Open Loop The lighting set point can be set to an absolute value useful in open loop sensor applications The absolute value selected becomes the maximum dimming set point 1 With the light on tap...

Страница 11: ...he light is dimming down up twice Press ON for three seconds 2 Click the switch ON 5 times to clear the switch click ON 5 times again to clear ALL switches and sensors and reset the controller to defa...

Страница 12: ...crease the timeout in 5 minute increments 4 To continue with configuration press ON for 3 seconds the light will resume dimming down up five times To exit Smart Click press OFF for 5 seconds Light Tim...

Страница 13: ...es past day lighting set point The lights will turn ON upon the next motion detected by the occupancy sensor When set for daylight harvesting operation the set point is used with a photo sensor light...

Страница 14: ...wn up nine times 2 Press ON for 3 seconds Default setting is 100 Adjust the maximum light level to the brightness level desired by clicking ON to increase and OFF to decrease in 2 increments 3 To cont...

Страница 15: ...Minimum Dimming Output enabled Motion sensor Time out 15 minutes Switch Time out no time out Auto ON Time out enabled with no linked switch disabled with linked rocker switch Light ON Set point 60 of...

Страница 16: ...rmful interference and ii this device must accept any interference received including interference that may cause undesired operation IC RSS 210 Contains IC 5713A STM300U echoflex Powered by ETC Echof...

Отзывы: