4 Installation
4.4 Installing
22
XP-503
12/2014 MN048014-EN www.eaton.com
4.4.5
Fixing and sealing
Built-in mounting in cabinets, etc.
The XP-503 is designed to be built-in mounted in control panels and swing frames.
CAUTION
The mounting cutout must be located in a position that ensures that webs or other
reinforcing elements in the control panel, etc. will stabilize it. If necessary,
reinforcing elements must be installed/added.
An IP65 degree of protection will only be ensured if the control panel is stiff enough,
the device is properly mounted using its holding brackets, and the gasket has a
proper seat.
Minimum sheet thickness of control panel panel where the device will be built-in
mounted: 1.5 mm.
In order for the device to be properly mounted, every single one of the holding
brackets included with the delivery must be used at its intended spot.
Example: XP-503-15
The following also applies to other device versions as applicable.
Device holding brackets
Polyurethane foam gasket
Abb. 3
Fixing and sealing