4 Installation
4.5 Preparing the device for operation
24
XP-503
12/2014 MN048014-EN www.eaton.com
4.5
Preparing the device for operation
CAUTION
Interference-proof connections for undisturbed operation
For all signal connections, use screened cables and metal connectors only.
All plug-in connections must be screwed or locked into place.
This will improve their electrical shielding.
Signal cables must not be routed in the same cable duct with power cables.
Before commissioning the system, check all cable connections.
Make sure that all voltages and signals have the required values.
CAUTION
Safely diverting electrical interference currents
The device and the control panel must be connected to a central earth point with as
short a conductor length as possible.
The connection between the device and the control panel must have as low a
resistance as possible.
The earth connection must be implemented using a green and yellow cable with a
minimum cross-sectional area of 6 mm².
Emitted interference as per EN 55022:2010 Class A and EN 61000-6-4:2007
Specifically for devices with a 24 VDC supply:
WARNING
Please note:
The device should only be run with safety extra-low voltage (functional extra-low
voltage with protective separation).
The power transformer must meet all applicable standards.
Содержание XP-503
Страница 1: ...Manual 12 2014 MN048014 EN XP 503 Panel PC...
Страница 6: ...1 General 1 3 Additional documentation 6 XP 503 12 2014 MN048014 EN www eaton com...
Страница 10: ...2 Description of device 2 4 Designation 10 XP 503 12 2014 MN048014 EN www eaton com...
Страница 18: ...3 Safety instructions 3 4 Device specific hazards 18 XP 503 12 2014 MN048014 EN www eaton com...
Страница 30: ...4 Installation 4 8 External connections 30 XP 503 12 2014 MN048014 EN www eaton com...