For more information visit:
www.EatonElectrical.com
EZ800/EZD Control Commands
MN05013001E
156
Example
The channel A parameters of 7-day time switch HW19 are to
be read.
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
81
80
1
Command: Read
92
–
Response: Read
successful
–
C2
2
Type
1C
1C
3
Instance
13
13
4 Index
02
02
5
Data 1
00
62
6
Data 2
00
0B
7
Data 3
00
7B
8
Data 4
00
25
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Date 2 = 0B
hex
Date 1 = 62
hex
ON
0
0
0
0
1
0
1
1
0
1
1
0
0
0
1
0
Weekday
Hour
Minute
Switch-on time:
Weekday = 01
hex
.. Monday
Hour = 0D
hex
.. 1300 hours
Minute = 22
hex
.. 34 minutes
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Date 4 = 25
hex
Date 3 = 7B
hex
OFF
0
0
1
0
0
1
0
1
0
1
1
1
1
0
1
1
Weekday
Hour
Minute
Switch-off time:
Weekday = 04
hex
.. Thursday
Hour = 15
hex
.. 2100 hours
Minute = 59
hex
.. 34 minutes
Содержание PROFIBUS-DP EZ204-DP
Страница 2: ......
Страница 9: ...For more information visit www EatonElectrical com MN05013001E 5 Glossary 193 Index 201 ...
Страница 10: ......
Страница 20: ......
Страница 28: ......
Страница 38: ......
Страница 184: ......
Страница 196: ......
Страница 204: ......
Страница 210: ......
Страница 211: ......