“Outputs 3 bytes” module: operating mode, R9
For more information visit:
www.EatonElectrical.com
MN05013001E
39
Table 3:
Byte 0: Operating mode
0 = status “0”, 1 = status “1”
Explanation
Value 34
hex
= 00110100
bin
:
This value sets the EZ/EZD status from STOP to RUN. It is
only interpreted as a command and therefore does not permit
an additional transfer of data. The index value 14
hex
must be
used in this situation.
Value 44
hex
= 01000100
bin
:
This value sets the EZ/EZD status from RUN to STOP. It is
also used only as command and it therefore works in the same
way as the RUN command.
EZ/EZD operating mode
Bit
7
6
5
4
3
2
1
0
Index for setting the basic unit to the safety
state
0
0
0
0
0
0
0
0
Index for transferring valid data
0
0
0
1
0
1
0
0
RUN command
0
0
1
1
0
1
0
0
STOP command
0
1
0
0
0
1
0
0