For more information visit:
www.EatonElectrical.com
Control commands for EZ700
MN05013001E
60
Markers: M1 – M16/N1 – N16
Unlike the write operation, the marker read operation reads
the entire marker area of a particular marker type (M or N) is
read.
Telegram structure
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
J
page 44
1
Command: Read
88
–
Response:
Read successful
–
C2
Command
rejected
–
C0
1
2
Len
01
01
3
Type
M marker
86
86
N marker
87
87
4
Index
2
00
00
5
Data 1 (Low Byte)
00
J
Table 15
6
Data 2 (Low Byte)
00
J
Table 15
7 – 8
Data 3 – 4
00
00
1) Possible causes
J
page 91
2) There are 16 M markers and 16 N markers. The markers are
addressed by Type and Index:
Use Type to select the M or N marker.
Use Index to select the marker number.
Содержание PROFIBUS-DP EZ204-DP