Read/write function block data
For more information visit:
www.EatonElectrical.com
MN05013001E
83
Table 34: Index 00 – Parameters
Example:
Data 1 (Byte 5) = 0xAC
Meaning:
The values appear in the Parameter menu. The time is used
in the impulse transmitter mode with the Second time base.
The time setpoint S1 is assigned a constant and the time
setpoint S2 is assigned a variable such as I7, I8 C2...etc.
Meaning
Bit 7
6
5
4
3
2
1
0
Appears in the parameter menu
Yes/no
0/1
Timer mode
On-delayed
0
0
0
Off-delayed
0
0
1
On-delayed with random setpoint
0
1
0
Off-delayed with random setpoint
0
1
1
On and off delayed
(two time setpoints)
1
0
0
On and off delayed each with random setpoint (two time
setpoints)
1
0
1
Impulse transmitter
1
1
0
Flashing relay (two time setpoints)
1
1
1
Time base
FB not used
0
0
Millisecond: S
0
1
Second: M:S
1
0
Minute: H:M
1
1
Use as constant and therefore can be written to
Time setpoint S1
0/1
Time setpoint S2
0/1