Control commands for EZ700
MN05013001E
68
Timing relays: T1 – T16
The following commands are used to read the logic state of
the individual timers T1 - T16.
Telegram structure
Table 20: Byte 5 to 6: Data 1 to 2
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
J
page 44
1
Command: Read
88
–
Response:
Read successful
–
C2
Command
rejected
–
C0
1
2
Len
01
01
3
Type
ED
ED
4
Index
00
00
5
Data 1 (Low Byte)
00
J
Table 20
6
Data 2 (Low Byte)
00
J
Table 20
7 – 8
Data 3 – 4
00
00
1) Possible causes
J
page 91
Data 1 Bit 7
6
5
4
3
2
1
0
T1
0/1
T2
0/1
...
...
T8
0/1
Data 2 Bit 7
6
5
4
3
2
1
0
T9
0/1
T10
0/1
...
...
T16
0/1