POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES
MN040041EN—August 2019 www.eaton.com
Chapter 7—Advanced application parameter
Table 165. Motor — P6.1, continued
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P6.1.17
Preheat Mode
0
2159
See Par ID 1346
P6.1.18
Preheat Control Source
31
2160
0 = DigIN:NormallyOpen
1 = DigIN:NormallyClose
2 = DigIN: 1
3 = DigIN: 2
4 = DigIN: 3
5 = DigIN: 4
6 = DigIN: 5
7 = DigIN: 6
8 = DigIN: 7
9 = DigIN: 8
10 = DigIN: A: IO1: 1
11 = DigIN: A: IO1: 2
12 = DigIN: A: IO1: 3
13 = DigIN: A: IO5: 1
14 = DigIN: A: IO5: 2
15 = DigIN: A: IO5: 3
16 = DigIN: A: IO5: 4
17 = DigIN: A: IO5: 5
18 = DigIN: A: IO5: 6
19 = DigIN: B: IO1: 1
20 = DigIN: B: IO1: 2
21 = DigIN: B: IO1: 3
22 = DigIN: B: IO5: 1
23 = DigIN: B: IO5: 2
24 = DigIN: B: IO5: 3
25 = DigIN: B: IO5: 4
26 = DigIN: B: IO5: 5
27 = DigIN: B: IO5: 6
28 = Time Channel 1
29 = Time Channel 2
30 = Time Channel 3
31 = Drive Temperature
32 = SlotA PT100
Temp Channel 1
33 = SlotA PT100
Temp Channel 2
34 = SlotA PT100 Temp Channel 3
35 = SlotA Max PT100 Temp
36 = SlotB PT100
Temp Channel 1
37 = SlotB PT100 Temp Channel 2
38 = SlotB PT100 Temp Channel 3
39 = SlotB Max PT100 Temp
40 = SlotA and SlotB Max PT100
Temp
P6.1.19
Preheat Enter Temp
0.0
19.9
ºC
10.0
2161
P6.1.20
Preheat Quit Temp
20.0
40.0
ºC
20.0
2162
P6.1.21
Preheat Output Volt
0.0
20.0
%
2.0
2163
Table 166. Drive — P6.2
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P6.2.1
Line Start Lockout
2
750
0 = Disabled, No Change
1 = Enable, No Change
2 = Disabled, Changed
3 = Enable, Changed
P6.2.2
Fault Reset Start
0
2483
0 = Start/Stop After Fault Reset
1 = Restart After Fault Reset
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.