71
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES
MN040041EN—August 2019 www.eaton.com
Chapter 6 — PID Application
Table 83. Brake — P4.2
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P4.2.1
DC-Brake Current
DriveNomCurrCT*15/100
DriveNomCurrCT*15/10 A
DriveNomCurrCT*1/2
254
P4.2.2
Start DC-Brake Time
0.00
600.00
s
0.00
263
P4.2.3
Stop DC-Brake Frequency
0.10
10.00
Hz
1.50
262
P4.2.4
Stop DC-Brake Time
0.00
600.00
s
0.00
255
P4.2.5
Brake Chopper Define
0
251
0 = Disabled
1 = B(Run) T(Rdy)
2 = External
3 = B(Rdy) T(Rdy)
4 = B(Run) T(No)
P4.2.6
Flux Brake
0
266
0 = Off
1 = On
P4.2.7
Flux Brake Current
ActiveMotorNomCurr*1/10 See Par ID 107
A
ActiveMotorNomCurr*1/2 265
Table 84. Skip Frequency — P4.3
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P4.3.1
Skip Range Ramp Factor
0.1
10.0
1.0
264
P4.3.2
Skip F1 Low Limit
0.00
See Par ID 257
Hz
0.00
256
P4.3.3
Skip F1 High Limit
See Par ID 256
400.00
Hz
0.00
257
P4.3.4
Skip F2 Low Limit
0.00
See Par ID 259
Hz
0.00
258
P4.3.5
Skip F2 High Limit
See Par ID 258
400.00
Hz
0.00
259
P4.3.6
Skip F3 Low Limit
0.00
See Par ID 261
Hz
0.00
260
P4.3.7
Skip F3 High Limit
See Par ID 260
400.00
Hz
0.00
261
Table 85. Energy Savings Calc — P4.4
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P4.4.1
Currency
0
2122
0 = $
1 = £
2 = €
3 = ¥
4 = Rs
5 = R$
6 = Fr
7 = kr
P4.4.2
Energy Cost
Varies
0.00
2123
P4.4.3
Data Type
0
2124
0 = Cumulative
1 = Daily Avg
2 = Weekly Avg
3 = Monthly Avg
4 = Yearly Avg
P4.4.4
Energy Savings Reset
2125
0 = Not Reset
1 = Reset
Motor Control
Table 86. Basic Setting — P5.1
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P5.1.1
Motor Control Mode
0
287
0 = Freq Control
1 = Speed Control
P5.1.2
Current Limit
DriveNomCurrCT*1/10
DriveNomCurrCT*2
A
DriveNomCurrCT*2
107
P5.1.3
V/Hz Optimization
0
109
See Par ID 1346
P5.1.4
V/Hz Ratio
3
108
0 = Linear
1 = Squared
2 = Programmable
3 = Flux Optimization
ote:
N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.
Input function is Level sensed.