POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES
MN040041EN—August 2019 www.eaton.com
Chapter 6 — PID Application
Feedback
Table 97. Basic — P7.4.1
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P7.4.1.1
PID1 Feedback Function
0
1330
0 = Source 1
1 = SQRT(Source 1)
2 = SQRT(Source 1 - Source 2)
3 = SQRT(Source 1) + SQRT(Source 2)
4 = Source 1 + Source 2
5 = Source 1 - Source 2
6 = MIN(Source 1,Source 2)
7 = MAX(Source 1,Source 2)
8 = MEAN(Source1,Source2)
P7.4.1.2
PID1 Feedback Gain
-1000.0
1000.0
%
100.0
1331
Table 98. Feedback 1 — P7.4.2
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P7.4.2.1
PID1 Feedback 1 Source
2
1332
0 = Not Used
1 = AI1
2 = AI2
3 = Slot A: AI1
4 = Slot B: AI1
5 = FB Process Data Input 1
6 = FB Process Data Input 2
7 = FB Process Data Input 3
8 = FB Process Data Input 4
9 = FB Process Data Input 5
10 = FB Process Data Input 6
11 = FB Process Data Input 7
12 = FB Process Data Input 8
13 = PT100 Temperture
14 = PID2 Output
15 = SlotA PT100 Temp Channel 1
16 = SlotA PT100 Temp Channel 2
17 = SlotA PT100 Temp Channel 3
18 = SlotB PT100 Temp Channel 1
19 = SlotB PT100 Temp Channel 2
20 = SlotB PT100 Temp Channel 3
21 = FB PID1 Feedback 1
22 = FB PID1 Feedback 2
P7.4.2.2
PID1 Feedback 1 Min
-200.00
200.00
%
0.00
1333
P7.4.2.3
PID1 Feedback 1 Max
-200.00
200.00
%
100.00
1334
Table 99. Feedback 2 — P7.4.3
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P7.4.3.1
PID1 Feedback 2 Source
0
1335
See Par ID 1332
P7.4.3.2
PID1 Feedback 2 Min
-200.00
200.00
%
0.00
1336
P7.4.3.3
PID1 Feedback 2 Max
-200.00
200.00
%
100.00
1337
ote:
N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.
Input function is Level sensed.