115
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES
MN040041EN—August 2019 www.eaton.com
Chapter 7—Advanced application parameter
Table 172. Setpoint 1 — P7.3.2
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P7.3.2.1
PID1 Set Point 1 Source
1
1312
0 = Not Used
1 = PID1 Keypad Set Point 1
2 = PID1 Keypad Set Point 2
3 = AI1
4 = AI2
5 = Slot A: AI1
6 = Slot B: AI1
7 = FB Process Data Input 1
8 = FB Process Data Input 2
9 = FB Process Data Input 3
10 = FB Process Data Input 4
11 = FB Process Data Input 5
12 = FB Process Data Input 6
13 = FB Process Data Input 7
14 = FB Process Data Input 8
15 = PID2 Output
16 = FB PID1 Set Point 1
17 = FB PID1 Set Point 2
P7.3.2.2
PID1 Set Point 1 Min
-200.00
200.00
%
0.00
1313
P7.3.2.3
PID1 Set Point 1 Max
-200.00
200.00
%
100.00
1314
P7.3.2.4
PID1 Set Point 1 Sleep Enable
0
1315
See Par ID 1346
P7.3.2.5
PID1 Set Point 1 Sleep Unit Sel
0
2396
0 = Output Frequency
1 = Motor Speed
2 = Motor Current
3 = PID1 Feedback
P7.3.2.6
PID1 Set Point 1 Sleep Level
Varies
0.00
2450
P7.3.2.7
PID1 Set Point 1 Sleep Delay
0
3000
s
0
1317
P7.3.2.8
PID1 Set Point 1 Wake
Up Level
-99999.99
99999.99
Varies
0.00
1318
P7.3.2.9
PID1 Set Point 1 Boost
-2.0
2.0
1.0
1320
P7.3.2.10
PID1 Set Point 1 Comp Enable
0
1352
See Par ID 1346
P7.3.2.11
PID1 Set Point 1 Comp Max
-200.00
200.00
%
0.00
1353
Table 173. Setpoint 2 — P7.3.3
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P7.3.3.1
PID1 Set Point 2 Source
2
1321
See Par ID 1312
P7.3.3.2
PID1 Set Point 2 Min
-200.00
200.00
%
0.00
1322
P7.3.3.3
PID1 Set Point 2 Max
-200.00
200.00
%
100.00
1323
P7.3.3.4
PID1 Set Point 2 Sleep Enable
0
1324
See Par ID 1346
P7.3.3.5
PID1 Set Point 2 Sleep Unit Sel
0
2397
See Par ID 2396
P7.3.3.6
PID1 Set Point 2 Sleep Level
Varies
0.00
2452
P7.3.3.7
PID1 Set Point 2 Sleep Delay
0
3000
s
0
1326
P7.3.3.8
PID1 Set Point 2 Wake Up
Level
-99999.99
99999.99
Varies
0.00
1327
P7.3.3.9
PID1 Set Point 2 Boost
-2.0
2.0
1.0
1329
P7.3.3.10
PID1 Set Point 2 Comp Enable
0
1354
See Par ID 1346
P7.3.3.11
PID1 Set Point 2 Comp Max
-200.00
200.00
%
0.00
1355
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.