5 Error messages
5.1 Introduction
DA1 Variable Frequency Drives
08/18 MN04020005Z-EN
www.eaton.com
137
5 Error messages
5.1 Introduction
The DA1 variable frequency drives have several internal monitoring
functions.
When a discrepancy from the proper operating conditions is detected, an
error message is displayed; the factory settings cause the relay contact to
open (control signal terminals 14 and 15).
5.1.1 Error messages
The most recent four error messages will be stored in the order in which
they occurred (with the most recent one in the first place). The error
messages can be read under monitor parameter P0-13.
The values are not deleted when there is a reset to factory settings !
5.1.2 Acknowledge error (Reset)
To acknowledge and reset the current error message, you can either switch
off the supply voltage or press the STOP pushbutton. Error messages can
also be reset with an additional positive edge at control signal terminal
2 (DI1) or 3 (DI2) (new start signal).
If parameter P2-36 is set from 2 (
Auto-1
) to 6 (
Auto-5
), the variable
frequency drive tries to restart automatically up to five times.