6 Specifications
6.1 General rating data
144
DA1 Variable Frequency Drives
08/18 MN04020005Z-EN
www.eaton.com
Overvoltage (surge, EN 61000-4-5: 2006)
110 - 115 V, 200 - 240 V
U
kV
±1, phase to phase/neutral conductor
±2, phase/neutral conductor to earth
380 - 480 V, 500 - 600 V
U
kV
±2, phase to phase
±4, phase to earth
Electric strength (flash, EN 61800-5-1: 2007)
110 - 115 V, 200 - 240 V
U
kV
1.5
380 - 480 V, 500 - 600 V
U
kV
2.5
Radio interference class (EMC)
Category and maximum screened motor cable length
with integrated radio interference suppression filter
C1
l
m
1
C2
l
m
5
C3
l
m
25
Installation position
Vertical
Installation altitude
h
m
0 - 1,000 above sea level,
> 1,000 with 1 % load current reduction every 100 m,
maximum 2,000 with UL approval,
maximum 4,000 without UL approval
Protection type
IP20 (NEMA 0)
IP55 (NEMA 3)
IP66 (NEMA 4X)
Fan (built-in)
Yes
Busbar tag shroud
BGV A3 (VBG4, finger and back-of-hand proof)
Main circuit / power section
Power supply
Rated operating voltage
DA1-12…
U
e
V
1~ 230 (200 V -10 % - 240 V +10 %)
DA1-32…
U
e
V
3~ 230 (200 V -10 % - 240 V +10 %)
DA1-34…
U
e
V
3~ 400 (380 V -10 % - 480 V +10 %)
DA1-35…
U
e
V
3~ 575 (500 V - 10 % - 600 V +10 %)
Mains frequency
f
Hz
50/60 ±10 %
Phase imbalance
%
max. 3
Maximum short-circuit current (supply voltage)
SCCR
kA
100 (according to IEC 60439-1)
Mains switch-on frequency
Maximum of once every 30 seconds
Mains network configuration (AC supply system)
TN and TT network with directly earthed neutral point.
IT earthing systems with PCM insulation monitoring
relays only.
Operation on phase-earthed networks is only
permissible up to a maximum phase-earth voltage of
300 V AC.
Specifications
Symbol
Unit
Value