3 Installation
3.6 Electrical Installation
DA1 Variable Frequency Drives
08/18 MN04020005Z-EN
www.eaton.com
121
3.6.2.12 IP66, control signal terminals (DA1-…-A6SC)
On DA1 variable frequency drives with IP66 protection and local controls
(DA1-…A6SC), the control signal terminals will be partially wired.
Figure 89: DA1-…-A6SC (factory connection)
When supplied, the control signal terminals will be connected as follows:
Table 17: Configuration of the control signal terminals
Terminal
Color
Function
1
RD (red)
+24 V to FWD/REV selector switch
2
BU (blue)
From selector switch = FWD
3
YE (yellow)
From selector switch = REV
5
GY (gray)
+10 V to potentiometer
6
WH (white)
From potentiometer = f-Set
7
BK (black)
From potentiometer = 0 V
→
For the enable signal for operation, you will also need to install
an insulated wire jumper from terminal 1 to terminal 12 (STO+)
and a link from terminal 13 (STO-) to terminal 9 or 7
(
PWR
OFF
ON
REV
FWD
0
1 2 3 4 5 6 7 8 9 10 11 12 13
BK
WH
GY
RD
BU
YE
1 2 3 4 5 6 7 8 9 10
12 13
11
+24 V
DI1
AI1
0 V
DI2
DI3
AO1
0 V
DI5
STO-
AO2
STO+
+10 V