6 Specifications
6.2 Specific rated operational data
150
DA1 Variable Frequency Drives
08/18 MN04020005Z-EN
www.eaton.com
DA1-32… series
Size
Symbol
Unit
030
046
061
072
090
110
Rated operational current
I
e
A
30
46
61
72
90
110
Overload current for 60 s every 600 s at 50 °C
I
L
A
58.5
69
91.5
108
135
165
Apparent power at rated operation
230 V
S
kVA
15.5
18.3
24.3
28.7
35.9
43.8
240 V
S
kVA
16.2
19.1
25.4
29.9
37.4
45.7
Rated motor output
230 V
P
kW
7.5
11
15
18.5
22
30
230 V
P
HP
10
15
20
25
30
40
Power input side (primary side):
Number of phases
three-phase
Rated voltage
U
LN
V
200 V - 10 % - 240 V +10 %, 50/60 Hz
(180 - 264 V ±0 %, 48 - 62 Hz ±0 %)
Input current (phase current)
I
LN
A
36.4
55.8
70.2
82.9
103.6
126.7
Minimum braking resistor
R
B
Ω
22
22
12
12
6
6
Switching frequency
Factory default setting
f
PWM
kHz
8
8
8
8
8
4
Settings range
f
PWM
kHz
4 - 24
4 - 24
4 - 24
4 - 24
4 -24
4 - 16
Maximum leakage current to earth (PE), without motor
I
PE
mA
1.42
1.42
0.28
0.28
1.54
1.54
Efficiency
η
0.97
(IP55)
0.96
(IP20)
0.97
0.97
0.97
0.97
0.97
Heat dissipation at I
e
P
V
W
187.5
(IP55)
410
(IP20)
264
345
518
550
720
Frame size
FS4
FS4
FS5
FS5
FS6
FS6