6 Specifications
6.2 Specific rated operational data
DA1 Variable Frequency Drives
08/18 MN04020005Z-EN
www.eaton.com
155
6.2.4 DA1-35… series
→
DA1-35… devices are not covered by the declaration of
conformity.
Additional radio interference suppression filters are required for
compliance.
Size
Symbol
Unit
2D1
3D1
4D1
6D5
9D0
012
Rated operational current
I
e
A
2.1
3.1
4.1
6.5
9
12
Overload current for 60 s every 600 s at 50 °C
I
L
A
3.15
4.65
6.15
9.75
13.5
18
Apparent power at rated operation
500 V
S
kVA
1.6
2.1
2.4
4.3
6
7.5
600 V
S
kVA
2
2.5
2.9
5.1
7.3
9
Rated motor output
500 V
P
kW
0.75
1.5
2.2
4
5.5
7.5
575 V
P
HP
1
2
3
5
7.5
10
Power input side (primary side):
Number of phases
three-phase
Rated voltage
U
LN
V
500 V -10 % - 600 V +10 %, 50/60 Hz
Input current (phase current)
I
LN
A
2.5
3.7
4.9
7.8
10.8
14.4
Minimum braking resistor
R
B
Ω
50
50
50
50
50
40
Switching frequency (pulse frequency)
Factory default setting
f
PWM
kHz
8
8
8
8
8
8
Settings range
f
PWM
kHz
4 - 24
4 - 24
4 - 24
4 - 24
4 - 24
4 - 24
Maximum leakage current to earth (PE), without motor
I
PE
mA
–
–
–
–
–
–
Efficiency
η
0.97
0.97
0.97
0.97
0.97
0.97
Heat dissipation at I
e
P
V
W
22.5
45
66
120
165
225
Frame size
FS2
FS2
FS2
FS2
FS2
FS3