OPERATION
Eaton 9140 UPS (7.5–10 kVA) User's Guide
S
164201622 Rev 3
www.eaton.com/powerquality
69
Starting the UPS on Battery
NOTE
Before using this feature, the UPS must have been powered by utility power at least
once.
To start the UPS on battery without utility power connected:
1.
Turn off all protected equipment before starting up the UPS.
2.
Switch all output circuit breakers to the ON (
|
) position.
3.
Press any button on the front panel display to activate the screen.
4.
Wait for the front panel LCD to illuminate.
The LCD displays the startup screen for five seconds, then displays
the system status screen. The fans run. The
indicator flashes
quickly then slowly, indicating that the UPS has entered Standby
mode.
5.
Select MENU from the system status screen, then select
CONTROL, OUTPUT CONTROL, UPS TO BATTERY, and OK to
confirm.
The LCD displays a confirmation message and the
indicator
illuminates solid. The UPS is now in Battery mode and supplying
battery power to your equipment.
6.
Turn on the protected equipment.
Содержание Powerware 9140
Страница 1: ...Powerware Series Eaton 9140 UPS 7 5 10 kVA User s Guide...
Страница 26: ...SAFETY WARNINGS Eaton 9140 UPS 7 5 10 kVA User s Guide S 164201622 Rev 3 www eaton com powerquality 20...
Страница 80: ...OPERATION Eaton 9140 UPS 7 5 10 kVA User s Guide S 164201622 Rev 3 www eaton com powerquality 74...
Страница 96: ...UPS MAINTENANCE Eaton 9140 UPS 7 5 10 kVA User s Guide S 164201622 Rev 3 www eaton com powerquality 90...
Страница 106: ...TROUBLESHOOTING Eaton 9140 UPS 7 5 10 kVA User s Guide S 164201622 Rev 3 www eaton com powerquality 100...