OPERATION
Eaton 9140 UPS (7.5–10 kVA) User's Guide
S
164201622 Rev 3
www.eaton.com/powerquality
64
User Settings
The following table displays the options that can be changed by the
user.
Table 5. User Settings
Description
Available Settings
Default Setting
O/P (Output) Frequency*
[50 Hz][60 Hz][Auto]
NOTE If Auto is selected, input frequencies
<55 Hz are set to 50 Hz, and input frequencies
>55 Hz are set to 60 Hz. O/P Frequency
changes from Auto to the sensed frequency
setting.
Auto
O/P (Output) Voltage
[200V][208V][220V][230V][240V][Auto]
NOTE If Auto is selected, input voltages
<220V are set to 208V, and input voltages
>220V are set to 230V. O/P Voltage changes
from Auto to the sensed voltage setting.
Auto
Buzzer Alarm
[Enabled][Disabled]
Enabled
Battery Pack
1 through 5
NOTE A value of 1 indicates the UPS internal
batteries only. See “Configuring the UPS for
EBMs” on page 72.
1
Battery Test
[Enabled][Disabled]
NOTE When Enabled, the battery test runs
automatically approximately every three
months.
Enabled
DC Start
[Enabled][Disabled]
Shipped: Disabled
After one startup and
shutdown sequence: Enabled
Auto Restart
[Enabled][Disabled]
Enabled
UPS ID
0 through 3
NOTE This option is not used.
0
* Changes to these options should be made before turning on the UPS (while the UPS is in Standby mode); otherwise,
the changes do not take effect.
Содержание Powerware 9140
Страница 1: ...Powerware Series Eaton 9140 UPS 7 5 10 kVA User s Guide...
Страница 26: ...SAFETY WARNINGS Eaton 9140 UPS 7 5 10 kVA User s Guide S 164201622 Rev 3 www eaton com powerquality 20...
Страница 80: ...OPERATION Eaton 9140 UPS 7 5 10 kVA User s Guide S 164201622 Rev 3 www eaton com powerquality 74...
Страница 96: ...UPS MAINTENANCE Eaton 9140 UPS 7 5 10 kVA User s Guide S 164201622 Rev 3 www eaton com powerquality 90...
Страница 106: ...TROUBLESHOOTING Eaton 9140 UPS 7 5 10 kVA User s Guide S 164201622 Rev 3 www eaton com powerquality 100...