INSTALLATION
Eaton 9140 UPS (7.5–10 kVA) User's Guide
S
164201622 Rev 3
www.eaton.com/powerquality
40
NOTE
To install the optional seismic mounting brackets, the length of the rails must be
between 28.5 and 32 inches.
16.
If installing the optional seismic mounting brackets, align the two
UPS seismic mounting brackets with the screw holes on the sides
of the UPS above the rear mounting brackets. Loosely secure the
brackets with the eight supplied wing bolts. See Figure 22.
Do not tighten the wing bolts.
Figure 22. Installing the Optional UPS Seismic Mounting Brackets