TROUBLESHOOTING
Eaton 9140 UPS (7.5–10 kVA) User's Guide
S
164201622 Rev 3
www.eaton.com/powerquality
97
Action
Possible Cause
Alarm or Condition
Power is not available at the
UPS output receptacles.
The UPS is in Standby mode.
Supply power to the connected equipment:
Turn the UPS on by selecting MENU from the
system status screen, then select CONTROL,
OUTPUT CONTROL, UPS TO ONLINE, and OK to
confirm.
The UPS does not start.
The main utility breaker is off.
Verify that the main utility breaker is on.
The power cord is not connected
correctly (plug-receptacle models).
Check the power cord connections.
The electronics module is being
replaced.
Complete the replacement procedure before
starting the UPS, or remove the utility power.
The UPS does not turn off.
The batteries or electronics module
is being replaced.
Complete the replacement procedure before
shutting down the UPS.
The UPS is powered (front
panel and fans are on), but
some or all of the protected
equipment is not on.
The equipment is not connected to
the UPS correctly.
Verify that the equipment is plugged into the
UPS receptacles. For hardwired models,
contact a qualified electrician to check
connections to the power source.
The REPO switch is active or the
REPO connector is missing.
Reset the REPO switch and restart the UPS.
Verify that the REPO connector is present.
Circuit breakers for UPS
receptacles are in the OFF position.
Switch UPS receptacle circuit breakers to the
ON position.
UPS receptacles have been turned
off by power management software
or a communication card.
Modify the settings in the power management
software or the communication card (refer to
the individual user's guide).
The UPS is in Standby mode.
Use the front panel to return the UPS to Normal
mode.
Battery test failed.
The batteries need service.
Contact your service representative.
Battery test did not run.
Load was less than 10% of rated
capacity when the battery test
started. Battery test report shows
CANCELLED, then changes to TEST
SCHED during the next appropriate
stage in the charging cycle.
The UPS automatically reschedules the battery
test.
User cancelled the battery test
through the front panel. Battery test
report shows CANCELLED.
Reschedule the battery test if necessary.
Battery charge cycle has not
completed.
Wait 48 hours.
Содержание Powerware 9140
Страница 1: ...Powerware Series Eaton 9140 UPS 7 5 10 kVA User s Guide...
Страница 26: ...SAFETY WARNINGS Eaton 9140 UPS 7 5 10 kVA User s Guide S 164201622 Rev 3 www eaton com powerquality 20...
Страница 80: ...OPERATION Eaton 9140 UPS 7 5 10 kVA User s Guide S 164201622 Rev 3 www eaton com powerquality 74...
Страница 96: ...UPS MAINTENANCE Eaton 9140 UPS 7 5 10 kVA User s Guide S 164201622 Rev 3 www eaton com powerquality 90...
Страница 106: ...TROUBLESHOOTING Eaton 9140 UPS 7 5 10 kVA User s Guide S 164201622 Rev 3 www eaton com powerquality 100...