9 Available protection settings
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN June 2018 www.eaton.com
slave action function successfully after the normal response by interrogating the trip unit,
for example, by reading its status. If the “slave action number” and its first complement
command is invalid, trip unit returns exception code 03.
Remote Control Date Format
control group
Definition
byte 2
byte 1
byte 0
Reset
Reset trip
0
0
2
Reset min/max currents
0
1
13
Reset min/max line-to-neutral voltages
0
1
15
Reset min/max line-to-line voltages
0
1
14
Reset peak demand watts
0
0
4
Reset all min/max values
0
1
4
Reset energy
0
0
8
Reset trip count
0
5
1
Reset operations count
0
1
2
Reset temperature
0
5
2
Reset runtime
0
1
3
Reset all diagnostics information
0
5
3
Reset powered up indication
0
0
3
Open breaker
0
0
1
Maintenance mode
Enable maintenance mode
1
0
8
Disable maintenance mode
1
0
9
Relay output
Activate relay output # YY
4
1
YY
De-activate relay output # YY
4
2
YY