9 Available protection settings
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN June 2018 www.eaton.com
Register
bit
field
mask
field
set points name
R/w
format
Value definition
403008
INCOM CAM baud rate
R
1 <--> 9600bps see IL01301033e
P8 "for series NRX INCOM
communication adapter module,
baud rate is fixed at 9600 baud and
represented by a value of 01"
403009
Ethernet CAM DHCP enable
R
0 <--> false
1 <--> true
403010
Ethernet CAM IP addr. MSB
R
0~255 <--> 0~255
403011
Ethernet CAM IP addr. LSB
R
0~255 <--> 0~255
403012
Ethernet CAM IP addr. MSB
R
0~255 <--> 0~255
403013
Ethernet CAM IP addr. LSB
R
0~255 <--> 0~255
403014
Ethernet CAM subnet mask
R
16~32 <--> 16~32
403015
Ethernet CAM default gateway
R
0~255 <--> 0~255
403016
Ethernet CAM default gateway
R
0~255 <--> 0~255
403017
Ethernet CAM reset pin
R
0~255 <--> 0~255
403018
Profibus CAM address
R
1~125 <--> 1~125
Set points group 4: I/O module group
Register
bit
field
mask
field
set points name
R/w
format Value definition
403000
15-0
0xFFFF
Password
W
Encoded Default “0000”
403001
15-0
0xFFFF
I/O module cfg
R/W Encoded 0x04FF
403002
15-0
Validity flags 0….15
R/W Encoded For each bit:
0 : corresponding parameter inactive
1 : corresponding parameter active
e.g. Bit 8 = 1
==> parameter 8 = active
403003
15-0
Validity flags 16….31
R/W Encoded For each bit:
0 : corresponding parameter inactive
1 : corresponding parameter active
e.g. Bit 8 = 1
==> parameter 8 = active
403004
15-0
0: digital output 0
R/W Encoded
403005
15-0
1: digital output 1
R/W Encoded
403006
2: digital output 2
R/W Encoded
403007
3: digital output 3
R/W Encoded
403008
4: S0 channel 0 type
R/W
0: output disabled
1: sends pulses based on active energy
2: sends pulses based on reactive energy
3: sends pulses based on apparent energy
403009
5: S0 channel 0 scale
R/W
0: sends a pulse every
1: W 1: sends a pulse every 10 W
2: sends a pulse every 100 W
3: sends a pulse every 1000 W
403010
6: S0 channel 0 pulse
R/W
pulse duration x *10 ms
range: 1…50 ==> 10…500 ms
403011
7: S0 channel 1 type
R/W
0: output disabled
1: sends pulses based on active energy
2: sends pulses based on reactive energy
3: sends pulses based on apparent energy
403012
8: S0 channel 1 scale
R/W
0: sends a pulse every
1 W 1: sends a pulse every 10 W
2: sends a pulse every 100 W
3: sends a pulse every 1000 W
403013
9: S0 channel 1 pulse
R/W
Pulse duration x *10 ms
Range: 1…50 ==> 10…500 ms
403014
10: Modbus address
R/W
Modbus ID (= device address)
permitted range: 1…255