9 Available protection settings
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN June 2018 www.eaton.com
9.2.23 PDG4 PXR25 and 20D settings
frame
800a
G styles
setting
ir
tr @ 6xir
isd (nxir)
tsd(s)
ii (nxin)
ig (nxin)
tg (s)
min
320
0.5
1.5
0.050
2
0.20
0.100
max
800
24.0
8.0
0.500
8.50
1.00
1.000
min
0.067
0.20
0.067
max
0.300
1.00
0.300
step
1.0
0.10
0.10
0.010
0.10
0.01
0.010
add'l opt
OFF
Flat
Trip
Flat
I
2
t
Alarm
I2t
9.2.24 PDC4 PXR25 and 20D settings
frame
800 a
1000 a
all
all
all
800
1000
G styles
setting
ir
tr @ 6xir
isd (nxir)
tsd(s)
ii (nxin)
ig (nxin)
tg (s)
min
320
400
0.5
1.5
0.050
2
2
0.20
0.100
max
800
1000
24.0
8.0
0.500
8.50
8.00
1.00
1.000
min2
0.067
0.20
0.067
max2
0.300
1.00
0.300
step
1.00
1.00
0.100
0.100
0.010
0.10
0.10
0.01
0.010
add'l opt
OFF
Flat
Trip
Flat
I
2
t
Alarm
I2t
9.2.25 PDG5 PXR20 settings
frame
800 a
1200 a
1600 a iec 800 a
1200/1600a all
all
800
1200
1600
G styles
setting
ir
tr @ 6xir
isd (nxir) tsd(s)
ii (nxin)
ig (nxin)
tg (s)
switch
1
2
3
4
5
6
7
1
320
500
800
0.5
0.5
1.5
0.050
2
2
2
0.20
0.100
2
350
550
900
1
1.0
2.0
0.100
3
3
2.5
0.30
0.150
3
400
600
1000
2
2.0
3.0
0.150
4
4
3
0.40
0.200
4
450
630
1100
4
4.0
4.0
0.200
5
5
3.5
0.60
0.300
5
500
700
1200
7
7.0
5.0
0.300
6
6
4
0.80
0.500
6
550
800
1250
8
10.0
6.0
0.400
8
7
5
1.00
0.750
7
600
900
1300
10
12.0
8.0
0.500
10
8
6
0.20
1.000
8
630
1000
1400
12
15.0
10.0
0.067
12
9
7
0.50
0.067
9
700
1100
1500
13
20.0
12.0
0.150
15
10
8
1.00
0.150
10
800
1200
1600
14
24.0
OFF
0.300
18.0
12.0
9.0
OFF
0.300
Flat
Trip
Flat
I
2
t
Alarm
I
2
t
Note that ground fault pickup will not exceed 1200 A