9 Available protection settings
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN June 2018 www.eaton.com
Register
bit
field
mask
field
set point
name
R/w format
Value definition
unit
403020
Ground
time(tg)
R/W Unsigned Ground fault time:
detail see the "PXR MCCB amp rating labels"
Tg = xxx / 1000 ( s )
Sec
403021
Ground fault
thermal
memory
R/W
Thermal memory enable/disable
LD thermal memory (powered and
unpowered operation. Used only in I
2
t and I
4
t)
0 = off
1 = cooling
403022
Neutral
protection
ratio
R/W Unsigned Neutral protection ratio:
0 <--> 0%
60 <--> 60%
100 <--> 100%
%
403023
High load
warning
R/W
High load alarm level
[50… 100] step 5
50%Ir...100%Ir
403024
GF_pre_alarm R/W
Ground Fault trip pre alarm pick up:
*100
[50…100] step 5
403025
reserved
(TBD)
Set points group 2: ModbusRTU group
Register
bit
field
mask
field
set points name
R/w
format
Value definition
units
403000
15-0
0xFFFF Password
W
Encoded default “0000”
403001
15-0
0xFFFF Group 2 = on-board Modbus
R/W
Encoded 0x02FF
403002
15-0
Integrated Modbus --
communication address
R/W
Encoded 001 - 246
403003
15-0
Integrated Modbus --
baudrate
R/W
Encoded 00 = 9600 bit/s
01 = 19200 bit/s
02 = 38400 bit/s
03 = 57600 bit/s
403003
15-0
Integrated Modbus --
parity
R/W
Encoded 00 = none
01 = odd
02 = even
403003
15-0
Integrated Modbus --
stop bit
R/W
Encoded 00 = 1 bit
01 = 2 bits
Set points group 3: CAM settings group
Register
bit
field
mask
field
set points name
R/w
format
Value definition
403000
15-0
0xFFFF
W
Encoded Default “0000”
403001
15-0
0xFFFF
R
Encoded 0x03FF
403002
15-0
CAM connection status
R
Encoded 0 = No external CAM
1 = External Modbus
2 = INCOM CAM
3 = Ethernet CAM
4 = Profibus CAM
403003
15-0
CAM communication address
R
Encoded 001~246 <--> 001~246
403004
15-0
CAM baud rate
R
Encoded 0 = 1200bps
1 = 4800bps
2 = 9600bps
3 = 19200bos
403005
15-0
CAM parity
R
Encoded 0 = None
1 = Odd
2 = Even
403006
CAM stopbit
R
0 = 1bit
1 = 2bits
403007
INCOM CAM address
R
0001~4094 <--> 0001~4094