background image

12

3  Protection setting description

PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs

   MN012007EN   June 2018   www.eaton.com

Ground (earth) sensing method

frame

sensor catalog #

Residual

PD2 – up to 100 A w/o bus-bar

PDG2XNCTD0100

PD2 – 100 to 225 A w/o bus-bar

PDG2XNCTD0225

PD2 – up to 100 A

PDG2XNCTB0100

PD2 – 100 to 225 A

PDG2XNCTB0225

PD3

PDG3XNCTB0600

PD4

PDG4XNCTB0800

PD5

PDG5XNCTB1200

PD6

PDG6XNCTB2500

Source ground / zero sequence

All

Tbd

3.5  Special consideration for ground fault test

3.5.1  NEC requirements and UL standards

The National Electric Code (NEC) under Article 230-95-C requires that any ground-fault 

protection system be performance tested when first installed.  UL Standard 489 amd 1053 

specify that instructions for ground fault testing accompany each ground fault protection 

system.  Please consult Instruction leaflet number IL012125EN available at www.eaton.com/

powerdefense to aid you in ground fault testing the Power Defense circuit breaker.

3.6  Maintenance mode protection

The PXR trip units support Eaton’s Arc Flash Reduction Maintenance System (ARMS), also 

known as maintenance mode.  When maintenance is being performed and the ARMS is 

enabled, the trip unit will trip the breaker with no intentional delay whenever the configured 

pickup level is exceeded.  The maintenance mode protection overlays the LSI protection 

functions and operates in parallel.  If maintenance mode causes the circuit breaker to trip, 

the “INST” indicator will be illuminated and the “Maintenance Mode Trip” message will be 

displayed if the style of trip unit has a display.
The maintenance mode pickup level setting is configured using the UI or PXPM software.  

They range from 2.5 (most protective) to 10, expressed as a multiplier of In.  The adjustable 

current settings allow for different levels of protection.  A higher level may be needed when, 

for example, another load fed from the ARMS protected breaker may contain motors that 

are being started and create large inrush currents over the lowest trip current level.  The 

selection of one of the reduction settings should be determined and selected by a person 

who is experienced in power system analysis.

3.6.1  Actuating and indicating maintenance mode protection

There are three ways to actuate the maintenance mode function, locally, remotely using a 

contact, or remotely using communications.  A blue LED on the trip unit always illuminates 

to confirm when the function is enabled.  

Содержание Power Xpert PD Series

Страница 1: ...MN012007EN Power Xpert Release the units for Power Defense molded case circuit breakers...

Страница 2: ...TNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENT...

Страница 3: ...fault settings 10 3 5 Special consideration for ground fault test 12 3 6 Maintenance mode protection 12 3 7 Override 13 3 8 Zone selective interlocking ZSI 13 3 9 Operating temperature 14 4 COMMUNICAT...

Страница 4: ...012007EN June 2018 www eaton com 9 AVAILABLE PROTECTION SETTINGS 24 9 1 Identifying the trip unit 24 9 2 Detailed settings tables 26 10 MODBUS COMMUNICATION PORT REGISTER MAP 36 10 1 Viewing setting M...

Страница 5: ...on settings Metering uses those same current sensors to monitor and record current In models that include voltage metering a full set of power and energy data is available with 1 accuracy Additionally...

Страница 6: ...0 2 Variable from 0 20 x In Pickup alarm only 3 settings 0 20 0 50 1 0 Variable from 0 20 tg Time delay flat 7 settings from 0 10 to 1 0 Variable from 0 10 to 1 0 Seconds Time delay I2 t 1 0 x In 3 se...

Страница 7: ...reactive demand peak Power kVA apparent demand peak Energy kWh total fwd rev VARh net VAh net Frequency Power factor 1 2 1 Metered data specifications Metered data accuracy is as follows Metered valu...

Страница 8: ...0 of life with all four bars shaded Each bar is approximately 25 of breaker health according to the algorithm As the life is decreased the shading in the leading bars will disappear An alarm will be g...

Страница 9: ...r remains off there is no auxiliary power applied or insufficient primary current to power the trip unit PXR trip units in MCCB will self power at 20 of the circuit breaker frame In 2 1 2 USB test and...

Страница 10: ...nance Mode and has two positions labeled OFF Remote and ON A blue light next to the maintenance mode switch illuminates when the ARMS protection is enabled ON ARMS is enabled locally and cannot be dis...

Страница 11: ...reaker mounted on its side the display is configurable to rotate 90 degrees left or right There are three navigation buttons near the display used to control the information shown on the display and t...

Страница 12: ...ion settings other configurable settings can be set using PXPM Details regarding the available protection settings for each frame are found in Section 9 Available protection settings Each switch has t...

Страница 13: ...placing any circuit breaker in operation set each trip unit protection setting to the values specified by the engineer responsible for the installation 3 1 Long delay pickup and time setting The PXR...

Страница 14: ...refer to the section on ZSI 3 3 Instantaneous pickup setting The instantaneous Ii setting is expressed as multiples of the circuit breaker frame rating In The instantaneous protection trips the break...

Страница 15: ...0 25 trip unit provides for three modes of sensing to detect ground fault currents residual source ground and zero sequence The mode is selected using the UI or by using the configuration software See...

Страница 16: ...When maintenance is being performed and the ARMS is enabled the trip unit will trip the breaker with no intentional delay whenever the configured pickup level is exceeded The maintenance mode protecti...

Страница 17: ...cause of trip 3 8 Zone selective interlocking ZSI The zone selective interlocking ZSI function is an option when ordering the circuit breaker ZSI functions in conjunction with the short delay and gro...

Страница 18: ...port configuration can be viewed and set using the user interface UI or using Power Xpert Protection Manager software The trip unit uses Modbus function codes 02 03 04 06 08 and 16 and supports up to...

Страница 19: ...ct to the external neutral current sensor N2 White Voltage sensor NV White grey Connect to the neutral sensor module and then the neutral bus Alarm relay s ALM1 Black white Normally open contacts clos...

Страница 20: ...djustable from 50 to 120 of Ir Note alarm1 alarm2 LED will BLINK current flow falls 5 below the set point Alarm high load alarm 1 current flow is greater than set point adjustable from 50 to 120 of Ir...

Страница 21: ...ration software Eaton s PXPM is a Microsoft Windows based software that configures controls monitors and tests Eaton PXR trip units The user can create modify and save configurations for a PXR trip un...

Страница 22: ...ser may work in offline mode and cannot edit the read only set point Change trip unit Takes user back to Create New Offline Setting Screen to modify trip unit s settings Save visible in open settings...

Страница 23: ...t parameters are highlighted in the exported PDF file Undo all changes Resets all set points to their original values 6 2 Remote control and test When service is required the remote control and test s...

Страница 24: ...pture waveform The PXR trip units allow user to manually capture both current and voltage waveforms by simply clicking the mouse A full cycle of waveform is captured and displayed in the PXPM software...

Страница 25: ...ing will require you to enter the four digit password The PXR trip unit has two built in functional test modes available for use One is a simulated current test and the other is an internal secondary...

Страница 26: ...of configuration and test results If desired make a copy and attach it to the interior of the circuit breaker cell door or another visible location This information should be used and maintained by th...

Страница 27: ...t points download Event Enter test mode Event exit test mode Event test complete Event enter maintenance mode Indicator also illuminates Event exit maintenance mode Event time change if 60 seconds Pre...

Страница 28: ...ction functions The 3 V lithium battery type CR1216 coin cell is easily removed and replaced pull to remove the battery tray remove the old battery from the holder replace with new one observe proper...

Страница 29: ...Relays E5Z PXR20 LSIG ARMS ZSI and relays E5M PXR20 LSIG ARMS Modbus and relays E5C PXR20 LSIG ARMS CAM and relays E5W PXR20 LSIG ARMS ZSI and Modbus and relays E5X PXR20 LSIG ARMS ZSI and CAM and rel...

Страница 30: ...Relay ready Modbus ready CAM onboard P8W PXR25 LSI motor Relay ready Modbus ready ZSI onboard P8Y PXR25 LSI motor Relay ready Modbus ready CAM onboard ZSI onboard P9M PXR25 LSIG motor Relay ready and...

Страница 31: ...xIr Ii nxIn Switch 1 2 1 16 25 40 50 63 10 2 2 2 2 2 2 18 32 50 63 80 10 3 3 3 3 3 3 20 40 63 80 100 10 4 4 4 4 4 4 25 50 70 90 125 10 5 5 5 5 5 5 32 55 80 100 150 10 6 6 6 6 6 6 40 63 90 125 160 10 8...

Страница 32: ...A 200 A 250 A G styles Setting Ir tr 6xIr Isd nxIr tsd s Ii nxIn Ig nxIn tg s Switch 1 2 3 4 5 6 7 1 16 25 40 50 63 0 5 1 5 0 050 2 2 2 2 2 0 20 0 100 2 18 32 50 63 80 1 0 2 0 0 100 3 3 3 3 3 0 30 0 1...

Страница 33: ...225 320 10 5 5 5 5 5 5 5 70 150 250 150 250 350 10 6 6 6 6 6 6 6 80 160 275 160 275 400 10 8 8 7 10 8 7 7 90 175 300 175 300 450 10 10 10 8 15 10 8 8 100 200 320 200 320 500 10 15 12 9 20 12 9 9 110 2...

Страница 34: ...00 150 200 360 10 4 0 I2 t 6 6 6 6 6 6 160 225 160 225 400 10 6 0 0 150 8 7 10 8 7 7 175 250 175 250 450 10 6 0 0 300 10 8 15 10 8 8 200 320 200 320 500 10 10 0 0 150 12 9 20 12 9 9 225 360 225 360 55...

Страница 35: ...400 630 24 0 OFF 0 300 17 6 11 0 28 8 18 0 11 4 OFF 0 300 Flat Trip Flat I2 t Alarm I2 t 9 2 15 PDG3 PXR25 and 20D settings Frame 3A 3B All 3A 3B G styles 125 A 250 A 400 A 250 A 400 A 630 A 125 A 250...

Страница 36: ...e 800 Setting Ir tr 6xIr Isd nxIr tsd s Ii nxIn Switch 1 2 3 1 320 10 2 0 0 150 2 2 350 10 2 0 0 300 3 3 400 10 2 0 I2 t 4 4 450 10 4 0 0 150 5 5 500 10 4 0 I2 t 6 6 550 10 6 0 0 150 6 5 7 600 10 6 0...

Страница 37: ...0 20 0 100 2 350 1 0 2 0 0 100 3 0 30 0 150 3 400 2 0 2 5 0 150 4 0 40 0 200 4 450 4 0 3 0 0 200 5 0 60 0 300 5 500 7 0 4 0 0 300 6 0 80 0 500 6 550 10 0 5 0 0 400 6 5 1 00 0 750 7 600 12 0 6 0 0 500...

Страница 38: ...Max2 0 300 1 00 0 300 Step 1 00 1 00 0 100 0 100 0 010 0 10 0 10 0 01 0 010 Add l opt OFF Flat Trip Flat I2 t Alarm I2t 9 2 25 PDG5 PXR20 settings Frame 800 A 1200 A 1600 A IEC 800 A 1200 1600A All Al...

Страница 39: ...0 2 0 0 100 3 3 2 5 0 30 0 150 3 900 1200 1800 2 0 3 0 3 0 2 5 0 150 4 4 3 0 40 0 200 4 1000 1250 1900 4 0 4 0 4 0 3 0 0 200 5 5 3 5 0 60 0 300 5 1100 1400 2000 7 0 5 0 5 0 3 5 0 300 6 6 4 0 80 0 500...

Страница 40: ...s definitions are defined the following table The first 16 bits are the actual status state while the late 16 bits indicate whether the corresponding status state is valid or supported by the trip uni...

Страница 41: ...97 406233 1258 1858 Real power peak demand W 1 404719 406255 126E 186E Product ID 404721 406257 1270 1870 Frequency Hz 100 406259 1872 Forward energy KWh 1 406261 1874 Reverse energy KWh 1 406263 1876...

Страница 42: ...trip count 1 404975 406511 136E 196E Total trip count 1 404977 406513 1370 1970 Test trip count 1 404979 406515 1372 1972 Open by comm count 1 404981 406517 1374 1974 Manual open count 1 404983 40651...

Страница 43: ...ite set points capabilities the set points group 0 1 2 should be written one by one using function code 06 the set points group four should be written the whole group using function code 16 Before rea...

Страница 44: ...0100 Maintenance mode state R Encoded 0 Off 1 On 0 0x0001 Maintenance mode remote control R W Encoded 0 Off 1 On 403007 2 0 0x0007 Arms level R W Encoded 1 2 5 In 2 4 In 3 6 In 4 8 In 5 10 In A 403008...

Страница 45: ..._ERROR_RELAY 0x0018 ALARM_BRK_HEALTH_RELAY 0x0019 ALARM_COMM_FAULT_RELAY 0x001A ALARM_ALL_RELAY 0x001B AUX_RELAY 0x0020 BELL_RELAY 0x0021 MM_ACTIVE_RELAY 0x0022 ZSI_ACTIVE_RELAY 0x0023 ZSI_INPUT_RELAY...

Страница 46: ...d for short delay and ground fault when enable for trip unit without G ZSI is implemented for short delay trip unit side 0 disable 1 enable 403008 0 1 0x0003 LD_slp R W Encoded long delay slope 0 I0 5...

Страница 47: ...e definition Units 403000 15 0 0xFFFF Password W Encoded default 0000 403001 15 0 0xFFFF Group 2 on board Modbus R W Encoded 0x02FF 403002 15 0 Integrated Modbus communication address R W Encoded 001...

Страница 48: ...R W Encoded For each bit 0 corresponding parameter inactive 1 corresponding parameter active e g Bit 8 1 parameter 8 active 403003 15 0 Validity flags 16 31 R W Encoded For each bit 0 corresponding p...

Страница 49: ...single triggering can place information into multiple event types For example the occur rence of an event triggered by a circuit breaker trip may provide both historical summary and historical trip in...

Страница 50: ...rmat of data 000016 000116 000416 000516 000616 408213 B0 R Object validity bit 408214 Encoded R Event Cause 00 Power up time OK 01 Set points download 02 Time adjusted 03 Trip 04 Alarm 05 Enter test...

Страница 51: ...Ground Sensing setting is 0 representing the ground current sensing type is residual ground current IG residual in address 408227 would be the actual value and IG source in address 408225 would be zer...

Страница 52: ...starting register number accesses an invalid object the illegal data object exception code 02 will be issued regardless of this configuration setting Non volatile register 402002 425346 0x07D1 0x6301...

Страница 53: ...up Definition Byte 2 Byte 1 Byte 0 Reset Reset trip 0 0 2 Reset min max currents 0 1 13 Reset min max line to neutral voltages 0 1 15 Reset min max line to line voltages 0 1 14 Reset peak demand watts...

Страница 54: ...diagnostics to monitor internal Modbus port communica tion with function code 08 For different sub function codes diagnostics information is listed below Sub function code Data Action 0 Echo query 1...

Страница 55: ...points error 0x004D Instantaneous 0x0003 Over temperature 0x004E Aux power under power 0x000E Long delay neutral over current 0x0050 Current un balance 0x0011 Ground fault 0x0054 Operations count 0x0...

Страница 56: ...B version ASCII 16 char 8 Example version of 01 02 0033 404591 0x11EE Reserved 16 Reserved Refer to 404606 0x11FD Reserved 404607 0x11FE Product ID Bit map 32 bit 2 ppppppvvvvdddddd Use division code...

Страница 57: ...53 9 Available protection settings PXR trip units for Power Defense molded case circuit breakers MN012007EN June 2018 www eaton com Notes...

Страница 58: ...rd Cleveland OH 44122 United States Eaton com 2018 Eaton All Rights Reserved Printed in USA Publication No MN012007EN TBG001403 June 2018 Eaton is a registered trademark All trademarks are property of...

Отзывы: