21
Installation
Safety Manual
MN042004EN March 2017 www.eaton.com
Common Technical Data Related to EMI/EMC
The C445 Motor Management Relay is considered Class A and
it complies with following standards.
Specification
Compliances with
Conducted Emissions Mains
CISPR 11/EN 55011:2010
Performance Criteria For Class A
limits
Radiated Emissions
CISPR 11/EN 55011 Performance
Criteria For Class A limits
Electrostatic Discharges
IEC 61000-4-2:2008 Severity Level 3
Radiated Immunity 80-2000 Mhz
IEC 61000-4-3:2010 Severity Level 3
Radiated Immunity 2000-2700 Mhz
IEC 61000-4-3:2010 Severity Level 1
Electrical Fast Transients
IEC 61000-4-4:2012 Severity Level 3
Surge
IEC 61000-4-5:2014 Severity Level 3
Conducted Immunity
IEC 61000-4-6:2013 Severity Level 3
Voltage Dips and Interruptions
IEC 61000-4-11:2004 and IEC
61000-4-29:2000 Severity Level 3
Power Frequency Magnetic Fields
IEC 61000-4-8:2009 Severity Level 3
Mounting
•
Mount the overload relay according to the Installation
Instruction details in Power Xpert® C445 User Manual.
•
Wire the motor cables.
Typical Wiring Diagrams
This section shows typical 2 wire diagrams. Three wire dia-
grams are shown in Appendix E - Field Wiring For Three Wire
and AC Applications in the User Manual.
Field Wiring for Overload Control
DIP X 10
USB
Motor
Status
“l1”: Field Input#1
“l2”: Field Input#2
“l3”: Field Input#3
“l4”: Field Input #4
“IC”: Input Common
“OV”: 24V Com
“24V”: +24V Out
1
2
3
4
5
6
7
1
2
3
4
1
2
3
JP2
JP1
“Q1”: K1 (NO)
“Q1”: K1 (NO)
“Q2”: K2 (NO)
“Q2”: K2 (NO)
“Q3”: K3 (NO)
“QC”: K3 Com
“Q3”: K3 (NC)
C445 Base Control
Module - 24VDC Inputs
Reset
Starter Relay
Source
Test Trip
Run
JP1
Field Wiring Configuration For Overload Control
CB Tripped
C445 Measurement Module
V1
V2
V3
Starter Relay
K1
CB On
M