Repair and Maintenance

Safety Manual

   MN042004EN   March 2017   www.eaton.com

Warranty

To meet the conditions of the warranty, you must observe 

all safety and commissioning instructions and the operating 

instructions.
If the overload relay is found to be non-operational within 

the warranty period or after the warranty period it should be 

returned to Eaton Corporation.

This can be done via the local contact person (www.eaton.

com/moeller/aftersales) or by calling the following number: 

+49(0)180-522-3822.

Installation

The appropriate installation instructions must be observed for 

the mechanical and electrical installation. The instruction leaflet 

(IL) along with user manual is included in the packaging and is 

also available on www.eaton.com/C445. 

 WARNING 

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC 

FLASH

•  Turn off all power supplying this equipment before 

working on it .

•  Apply appropriate personal protective equipment 

(PPE) and follow safe electrical work practices .

Failure to follow these instructions can result in death 

or serious injury .

 CAUTION 

For explosion protection, a MANUAL RESET is only 

permissible after the motor has cooled down or by 

automatic switching using a control interlock to the motor 

or electrical machine. Resets may be carried out during the 

installation or by trained personnel in the control room.

 CAUTION 

An automatic restart is not recommended for Ex e 

applications after the control voltage has failed and then 

been restored. 

 

 

Failure Mode Definitions

1.  Safe Detected: The motor management relay software 

detects and changes the relay state for the random hard-

ware failures not impacting safety function performance.

2.  Safe Undetected: The motor management relay software 

may not detect the random hardware failures which do not 

impact the safety function performance.

3.  Dangerous Detected: The motor management relay soft-

ware detects and changes the relay state for the random 

hardware failure impacting safety function performance.

4.  Dangerous Undetected: The motor management relay soft-

ware may not detect the random hardware failures which 

may impact safety function performance.

Repair and Maintenance

User shall refer to APPENDIX C - TROUBLESHOOTING AND 

DIAGNOSTICS section of C445 user manual to understand vari-

ous fault codes and troubleshooting options. 

 WARNING 

UNINTENDED EQUIPMENT OPERATION

The maintenance of this product requires expertise 

in the design and programming of control systems . 

Only persons with such expertise should be allowed 

to program, install, maintain, and apply this product . 

Follow all local and national safety codes and standards .

Failure to follow these instructions can result in death, 

serious injury, or equipment damage .

The Power Xpert® C445 motor management relay shall 

undergo a proof test during regular maintenance operation 

at least every 1 year. The proof test procedure is explained 

in the Installation and Operation manual.

If a device is observed to be failed during a maintenance 

check, it shall be taken out of operation and returned to 

Eaton.

This can be done via the local contact person (www.eaton.

com/moeller/aftersales) or by calling the following number: 

+49(0)180-522-3822.

 CAUTION 

Faulty devices shall not be opened or repaired. They must 

be replaced by specialist personnel.

 WARNING 

Do not service with voltage applied - Lock-out Tags .

Содержание Power Xpert C445

Страница 1: ...Safety Manual Effective March 2017 Power Xpert C445 global motor management relay...

Страница 2: ...THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY A...

Страница 3: ...d information on local distributors or Eaton s sales offices Website Address www eaton com c445 EatonCare Customer Support Center Call the EatonCare Support Center if you need assistance with placing...

Страница 4: ...e Contact iii SAFETY CONSIDERATIONS VI Definitions and Symbols vi Hazardous High Voltage vi Warnings and Cautions vi About this Manual 1 Power Xpert C445 Motor Management Relay 1 Power Xpert C445 Syst...

Страница 5: ...a Related to EMI EMC 21 Mounting 21 Typical Wiring Diagrams 21 Device Settings 22 TEST OF THE RELAYS 23 Operational Status Signaling 23 Base Control Module LED Behavior 23 Measurement Module LED Behav...

Страница 6: ...nents with housings or protrusions at or above line potential Extreme care should be taken to protect against shock Stand on an insulating pad and make it a habit to use only one hand when checking co...

Страница 7: ...n about the Power Xpert C445 can be found on the Eaton Website www eaton eu or www eaton com Power Xpert C445 Motor Management Relay Foreword In addition to the regulations in accordance with EN 60079...

Страница 8: ...port switch C445XC E PROFIBUS DPV1 module C445XC P for any purpose when C445 system is commissioned to protect motors installed in hazardous area CAUTION The C445 system is meant to be used for secure...

Страница 9: ...ommunication cards Provides battery backed up fault time stamping and non volatile memory for configuration parameters Communication Modules Optional modules to provide com munications PROFIBUS DVP0 a...

Страница 10: ...e relay s inputs and outputs Active Operation Mode The Active Operation Mode parameter is used to select the active mode Any change to this parameter will require a soft reset or power cycle before th...

Страница 11: ...reverser Output 3 is a user configurable output whose function can be changed by the user Start Delta Operation Mode Description The Star Delta starter control provides the logic to control a Star De...

Страница 12: ...allowing the motor time to slow down before transitioning to the slow speed The C445 will issue a control fault when The RunSlow or RunFast command is active and phase volt age is present and no phase...

Страница 13: ...o closed feedback is detected A De energize command is active and no open feedback is detected Output 1 will be de activated when the C445 experiences a fault inhibit condition Output 1 solenoid coil...

Страница 14: ...t Operation Mode The C445 can operate as general purpose I O providing the user 4 discrete inputs and 3 discrete outputs that can be con trolled over a fieldbus network The inputs on the Base Control...

Страница 15: ...ng Supply Voltage A 120 240 Vac D 24 Vdc Version S Standard X ATEX Inputs A 120 Vac D 24 Vdc Options N None M On board Modbus RS 485 ab ab a For other communictation protocol options please see Access...

Страница 16: ...d to connect the base con trol module to the measurement module and to the user inter face Use the appropriate lengths for each connection Description Catalog Number Connection cable base control modu...

Страница 17: ...0 2 2 5 mm 24 12 AWG 0 4 0 5 Nm 3 5 4 4 lb in Us 120 240 Vac Cat No Style No C445 Base Control Module 120 240VAC Powered Standard 120VAC Inputs Latching Output Modbus RTU Serial No 123456789012 Aux Co...

Страница 18: ...NUAL RESET button is located on the faceplate of the unit Depressing this button will clear any Overload fault that has been latched but is no longer present thermal capacity must be less than 100 Res...

Страница 19: ...be fed on all three poles to prevent early tripping Measurement Precondition Imax 50 of FLA Imin 25 of FLA No V Phase Loss or no voltage option Measurement Parameter Current unbalance percent Protect...

Страница 20: ...MB072 3 21 6 3 C445MC090 3 27 3 C445MC136 34 40 8 34 C445M EXT 30 of CT Primary 50 of CT Primary 50 of CT Primary Fault Warning 1061 2 1079 Fault Trip Delay At powerup 0 5 0 1062 Use Fault Trip Inhibi...

Страница 21: ...e electric motor must first cool down from the heat produced by the overload before it can be switched on again The C445 motor management relay reset can be achieved by either MANUAL RESET and auto re...

Страница 22: ...egister 600 Overload Fieldbus Control Word The Overload control profile accepts the following control com mands from a control network 7 6 5 4 3 2 1 0 TEST TRIP RESET Possible control commands 0x01 TE...

Страница 23: ...ction The C445XX P Profibus Communication Card shall detect any of the events listed below as loss of communication with master device and inform BCM C445BX XXXX as communication loss by invoking syst...

Страница 24: ...285 0 364605 0 276269 0 210949 Failure rate for undetected safe failures SU 2 1 326801 1 394441 1 597322 1 529682 Failure rate for detected dangerous failures DD 3 0 000423 0 000426 0 000426 0 000426...

Страница 25: ...7 796069 Average probability of failure on demand PFDAVG 3 687 X 10 07 2 113 X 10 07 2 101 X 10 07 3 675 X 10 07 Architecture 1oo1 1oo1 1oo1 1oo1 Lifetime 20 Yrs 20 Yrs 20 Yrs 20 Yrs Proof Test Interv...

Страница 26: ...e relay state for the random hard ware failures not impacting safety function performance 2 Safe Undetected The motor management relay software may not detect the random hardware failures which do not...

Страница 27: ...vel 3 Voltage Dips and Interruptions IEC 61000 4 11 2004 and IEC 61000 4 29 2000 Severity Level 3 Power Frequency Magnetic Fields IEC 61000 4 8 2009 Severity Level 3 Mounting Mount the overload relay...

Страница 28: ...CONTROL The designer of any control scheme must consider the potential failure modes of control paths and for certain critical functions provide a means to achieve a safe state during and after a path...

Страница 29: ...nput Inactive An LED test is performed after every reset or whenever commanded to from the network LED tests will cycle through both colors on bicolor LEDs The test lasts 2 seconds Output Status LEDs...

Страница 30: ...ent relay provides users with a convenient method for checking the complete motor pro tection modules measurement module base control module communication cards For example this check can be used to c...

Страница 31: ...dule the Proof Test can be performed as stated in the table that follows Profibus Modbus TCP BCM Fieldbus RS485 Ethernet IP Invoking Proof Test Service Configure System Services register Slot 0 index...

Страница 32: ...and rec ommendations in the user documentation All information associated with any field failures of this product should be collected under a dependability man agement process e g IEC 60300 3 2 and r...

Страница 33: ...27 Conditions of Safe Use controlled by Eaton drawing 464 1025 Safety Manual MN042004EN March 2017 www eaton com Notes...

Страница 34: ...rchaser or user by its customers resulting from the use of the information recom mendations and description contained herein Licenses This product includes embedded software that incorporates or inter...

Отзывы: