Safety Considerations  

Safety Manual

   MN042004EN   March 2017   www.eaton.com

The C445 will issue a control fault when:

• 

The RunSlow or RunFast command is active and phase volt-

age is present and no phase current is detected.

• 

A Stop command is active and current is detected.

ote:

N

Even with the control fault disabled, after de-activating the pres-

ent speed, the C445 will NOT transition to the new speed until current 

readings decrease to zero.

• 

Outputs 1 and 2 will be de-activated anytime the C445 expe-

riences a fault/inhibit condition.

• 

Output 1 – slow starter coil (NO)

• 

Output 2 – fast starter coil (NO)

• 

Output 3 – open for user configuration and their function can 

be selected by the user.

The AtRef (At Reference) bit in the Motor Control Status regis-

ter is set based on the following two conditions. At Reference 

signals that the motor is up to speed.
1.  If motor current first exceeds 115% of the active overload 

FLA rating and then decreases back below 115% of the 

active overload FLA rating, it is determined the motor has 

come up to speed and the AtRef bit will be set.

2.  If motor current exceed s 30% of the active overload FLA 

rating and remains until after the Motor State Transition to 

Run Delay from Start time expires the motor is determined 

to be up to speed and the AtRef bit will be set.  

Two Speed Dahlander Operation Mode

The Two Speed Dahlander motor starter operation mode 

accepts off/slow/fast commands to control two speed motor 

applications. A run slow command will activate Output 1(slow). 

A run fast command will activate Output 3(net). Then after the 

Network Contactor Delay time expires, Output 2(fast) activates 

starting the motor on the fast winding. A stop command de-

activates all 3 outputs.
When transitioning from fast -> slow, the C445 will de-activate 

both Output 2(fast) and Output 3(net) and will delay activating 

Output 1(slow) until the Control Switching Time Delay expires 

allowing the motor time to slow down before transitioning to 

the slow speed.

The C445 will issue a control fault when:

• 

The RunSlow or RunFast command is active and phase volt-

age is present and no phase current is detected.

• 

A Stop command is active and current is detected.

ote:

N

Even with the control fault disabled, after de-activating the pres-

ent speed, the C445 will NOT transition to the new speed until current 

readings decrease to zero.

• 

Outputs 1, 2 and 3 will be de-activated anytime the C445 

experiences a fault/inhibit condition.

• 

Output 1 – slow starter coil (NO)

• 

Output 2 – fast starter coil (NO)

• 

Output 3 – net starter coil (NO)

The AtRef (At Reference) bit in the Motor Control Status regis-

ter is set based on the following two conditions. At Reference 

signals that the motor is up to speed.
1.  If motor current first exceeds 115% of the active overload 

FLA rating and then decreases back below 115% of the 

active overload FLA rating, it is determined the motor has 

come up to speed and the AtRef bit will be set.

2.  IF motor current exceeds 30% of the active overload FLA 

rating and remains until after the Motor State Transition to 

Run Delay from Start time expires the motor is determined 

to be up to speed and the AtRef bit will be set. 

 

Auto Transformer Operation Mode

The auto transformer reduced voltage motor starter profile 

accepts start/stop commands to control motors wired in a 

reduced voltage auto transformer configuration. When a start 

command is received Output 3(star) will be activated. Then 

after the Network Contactor Delay time expires, Output 1(start) 

activates starting the motor with the reduced voltage from the 

auto transformer. When the C445 detects the motor is up to 

speed or the Maximum Star Winding Time expires, whichever 

occurs first, the Network Contactor Delay timer is started and 

Output 3 is de-activated. After the Network Contactor Delay 

time expires, Output 2(run) also activates, which transitions the 

transformer to full voltage. After a second Network Contactor 

Delay time expires, Output 1(start) de-activates placing the con-

trol into full voltage run mode.

Содержание Power Xpert C445

Страница 1: ...Safety Manual Effective March 2017 Power Xpert C445 global motor management relay...

Страница 2: ...THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY A...

Страница 3: ...d information on local distributors or Eaton s sales offices Website Address www eaton com c445 EatonCare Customer Support Center Call the EatonCare Support Center if you need assistance with placing...

Страница 4: ...e Contact iii SAFETY CONSIDERATIONS VI Definitions and Symbols vi Hazardous High Voltage vi Warnings and Cautions vi About this Manual 1 Power Xpert C445 Motor Management Relay 1 Power Xpert C445 Syst...

Страница 5: ...a Related to EMI EMC 21 Mounting 21 Typical Wiring Diagrams 21 Device Settings 22 TEST OF THE RELAYS 23 Operational Status Signaling 23 Base Control Module LED Behavior 23 Measurement Module LED Behav...

Страница 6: ...nents with housings or protrusions at or above line potential Extreme care should be taken to protect against shock Stand on an insulating pad and make it a habit to use only one hand when checking co...

Страница 7: ...n about the Power Xpert C445 can be found on the Eaton Website www eaton eu or www eaton com Power Xpert C445 Motor Management Relay Foreword In addition to the regulations in accordance with EN 60079...

Страница 8: ...port switch C445XC E PROFIBUS DPV1 module C445XC P for any purpose when C445 system is commissioned to protect motors installed in hazardous area CAUTION The C445 system is meant to be used for secure...

Страница 9: ...ommunication cards Provides battery backed up fault time stamping and non volatile memory for configuration parameters Communication Modules Optional modules to provide com munications PROFIBUS DVP0 a...

Страница 10: ...e relay s inputs and outputs Active Operation Mode The Active Operation Mode parameter is used to select the active mode Any change to this parameter will require a soft reset or power cycle before th...

Страница 11: ...reverser Output 3 is a user configurable output whose function can be changed by the user Start Delta Operation Mode Description The Star Delta starter control provides the logic to control a Star De...

Страница 12: ...allowing the motor time to slow down before transitioning to the slow speed The C445 will issue a control fault when The RunSlow or RunFast command is active and phase volt age is present and no phase...

Страница 13: ...o closed feedback is detected A De energize command is active and no open feedback is detected Output 1 will be de activated when the C445 experiences a fault inhibit condition Output 1 solenoid coil...

Страница 14: ...t Operation Mode The C445 can operate as general purpose I O providing the user 4 discrete inputs and 3 discrete outputs that can be con trolled over a fieldbus network The inputs on the Base Control...

Страница 15: ...ng Supply Voltage A 120 240 Vac D 24 Vdc Version S Standard X ATEX Inputs A 120 Vac D 24 Vdc Options N None M On board Modbus RS 485 ab ab a For other communictation protocol options please see Access...

Страница 16: ...d to connect the base con trol module to the measurement module and to the user inter face Use the appropriate lengths for each connection Description Catalog Number Connection cable base control modu...

Страница 17: ...0 2 2 5 mm 24 12 AWG 0 4 0 5 Nm 3 5 4 4 lb in Us 120 240 Vac Cat No Style No C445 Base Control Module 120 240VAC Powered Standard 120VAC Inputs Latching Output Modbus RTU Serial No 123456789012 Aux Co...

Страница 18: ...NUAL RESET button is located on the faceplate of the unit Depressing this button will clear any Overload fault that has been latched but is no longer present thermal capacity must be less than 100 Res...

Страница 19: ...be fed on all three poles to prevent early tripping Measurement Precondition Imax 50 of FLA Imin 25 of FLA No V Phase Loss or no voltage option Measurement Parameter Current unbalance percent Protect...

Страница 20: ...MB072 3 21 6 3 C445MC090 3 27 3 C445MC136 34 40 8 34 C445M EXT 30 of CT Primary 50 of CT Primary 50 of CT Primary Fault Warning 1061 2 1079 Fault Trip Delay At powerup 0 5 0 1062 Use Fault Trip Inhibi...

Страница 21: ...e electric motor must first cool down from the heat produced by the overload before it can be switched on again The C445 motor management relay reset can be achieved by either MANUAL RESET and auto re...

Страница 22: ...egister 600 Overload Fieldbus Control Word The Overload control profile accepts the following control com mands from a control network 7 6 5 4 3 2 1 0 TEST TRIP RESET Possible control commands 0x01 TE...

Страница 23: ...ction The C445XX P Profibus Communication Card shall detect any of the events listed below as loss of communication with master device and inform BCM C445BX XXXX as communication loss by invoking syst...

Страница 24: ...285 0 364605 0 276269 0 210949 Failure rate for undetected safe failures SU 2 1 326801 1 394441 1 597322 1 529682 Failure rate for detected dangerous failures DD 3 0 000423 0 000426 0 000426 0 000426...

Страница 25: ...7 796069 Average probability of failure on demand PFDAVG 3 687 X 10 07 2 113 X 10 07 2 101 X 10 07 3 675 X 10 07 Architecture 1oo1 1oo1 1oo1 1oo1 Lifetime 20 Yrs 20 Yrs 20 Yrs 20 Yrs Proof Test Interv...

Страница 26: ...e relay state for the random hard ware failures not impacting safety function performance 2 Safe Undetected The motor management relay software may not detect the random hardware failures which do not...

Страница 27: ...vel 3 Voltage Dips and Interruptions IEC 61000 4 11 2004 and IEC 61000 4 29 2000 Severity Level 3 Power Frequency Magnetic Fields IEC 61000 4 8 2009 Severity Level 3 Mounting Mount the overload relay...

Страница 28: ...CONTROL The designer of any control scheme must consider the potential failure modes of control paths and for certain critical functions provide a means to achieve a safe state during and after a path...

Страница 29: ...nput Inactive An LED test is performed after every reset or whenever commanded to from the network LED tests will cycle through both colors on bicolor LEDs The test lasts 2 seconds Output Status LEDs...

Страница 30: ...ent relay provides users with a convenient method for checking the complete motor pro tection modules measurement module base control module communication cards For example this check can be used to c...

Страница 31: ...dule the Proof Test can be performed as stated in the table that follows Profibus Modbus TCP BCM Fieldbus RS485 Ethernet IP Invoking Proof Test Service Configure System Services register Slot 0 index...

Страница 32: ...and rec ommendations in the user documentation All information associated with any field failures of this product should be collected under a dependability man agement process e g IEC 60300 3 2 and r...

Страница 33: ...27 Conditions of Safe Use controlled by Eaton drawing 464 1025 Safety Manual MN042004EN March 2017 www eaton com Notes...

Страница 34: ...rchaser or user by its customers resulting from the use of the information recom mendations and description contained herein Licenses This product includes embedded software that incorporates or inter...