155
10 Product specifications
10.1 Model numbers
The UPS systems are housed in free-standing cabinets with safety shields behind the doors. The UPS
systems are available in 50/60 Hz with various output power ratings.
The following sections detail the input, output, environmental, and battery specifications for the UPS.
10.2 Single module specifications
10.2.1 UPS system input
10.2.2 UPS system output
Models
Power Rating
Frequency
9395P 250 kVA
250 kVA PF 1.0
50/60 Hz
9395P
275
kVA
275
kVA PF
1.0
50/60 Hz
Operating Input Voltage
(N –15%)
400 Vac for operation from 340 Vac to 460 Vac
Operating Input Frequency Range
±5 Hz
Operating Input Current
See Table 3-4. Reduced for
Generator Adjustable
Input Current Harmonic Content
< 3% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 61000-4-5
Battery Voltage
480 Vdc
UPS Output Capacity
100% rated current
Output Voltage Regulation
±10% dynamic, ±1.5% steady state
Output Voltage Adjustment (N/–3%)
380 Vac nominal, adjustable from 368.6 Vac to 391.4 Vac
400 Vac nominal, adjustable from 388 Vac to 412 Vac
415 Vac nominal, adjustable from 402.5 Vac to 427.5 Vac
Output Voltage Harmonic Content
1.5% max THD (linear load)
5% max THD (nonlinear load)
Output Current
9395P 250 kVA / 275 kVA / 300 kVA
User’s and Installation Guide
9395P 300 kVA
300 kVA PF 0.9
50/60 Hz
Содержание Power Xpert 9395P 250 kVA
Страница 1: ...User s and Installation Guide Power Xpert 9395P UPS 250 kVA 275 kVA 300 kVA...
Страница 2: ......
Страница 3: ...Power Xpert 9395P UPS 250 kVA 275 kVA 300 kVA User s and Installation Guide...
Страница 168: ......
Страница 169: ......
Страница 170: ...614 01919 00...