9395P 250 kVA / 275 kVA / 300 kVA
User’s and Installation Guide
Table 7
-8
. Command Menu
Operation
Function
Subfunction
Operation
UPS Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired,
then press the SELECT pushbutton to execute the command or proceed to further
command screens.
Go to Online
Starts the UPS in Online mode or transfers the UPS to Online mode from Bypass mode.
Enable (Disable) Energy Saver
Enables or disables Energy Saver System mode. Enable changes to Disable when
the Energy Saver System mode is enabled.
Enables or disables the Variable Module Management System mode. Enable changes
to Disable when the Variable Module Management System mode is enabled.
Enable (Disable) Var Module
Management
Start High Alert
Starts High Alert mode.
Go to Bypass
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Online
mode.
Load Off
Displays the Load Off screen (see paragraph 7.
4
.7).
Bypass
Commands
Use the up or down arrow pushbutton to highlight the command function desired,
then press the SELECT pushbutton to execute the command or proceed to further
command screens.
Go to Bypass
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Online
mode.
Go to Online
Starts the UPS in Online mode or transfers the UPS to Online mode from Bypass mode.
Enable (Disable) Energy Saver
Enables or disables Energy Saver System mode. Enable changes to Disable when
the Energy Saver System mode is enabled.
Enables or disables the Variable Module Management System mode. Enable changes
to Disable when the Variable Module Management System mode is enabled.
Enable (Disable) Var Module
Management
Start High Alert
Starts High Alert mode.
Load Off
Displays the Load Off screen (see paragraph 7.
4
.7).
Charger Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired,
then press the SELECT pushbutton to execute the command.
Charger On
Turns the battery charger on.
Charger Off
Turns the battery charger off.
UPM Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired,
then press the SELECT pushbutton to execute the command.
UPM On
Turns the UPM on without transferring the load to Online mode. The Load is on
bypass.
UPM Off
Transfers the load to bypass and turns the UPM off.
UPM Go to Online
Turns the UPM on and transfers the load to Online mode.
Charger On
Turns the battery charger on.
Charger Off
Turns the battery charger off.
NOTE The Energy Saver System and Variable Module Management System mode commands are displayed only if
enabled at the factory or by an Eaton Customer Service Engineer
.
NOTE Variable Module Management System and Energy Saver System modes are mutually exclusive.