117
9395P 250 kVA / 275 kVA / 300 kVA
User’s and Installation Guide
7.5.12
Enable Variable Module Management System Mode from the Bypass
Command Menu
To enable Variable Module Management System mode:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is
displayed.
2.
On the System Status screen, select the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass Control
Command
screen is displayed.
4.
On the Bypass Control Command screen, select
ENABLE VAR MODULE MANAGEMENT
.
5.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Variable Module Management System mode. In
approximately
twenty seconds the UPS calculates the required number of UPMs needed
to support the load.
The Online status indicator is illuminated. The UPS status indicates VMMS.
The UPM status
indicates ONLINE.
7.5.13
Disable Variable Module Management System Mode from the
Bypass
Command Menu
To
disable
Variable
Module
Management
System
mode:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is
displayed.
2.
On the System Status screen, select the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass Control
Command screen
is displayed.
4.
On the Bypass Control Command screen, select
DISABLE VAR MODULE MANAGEMENT
.
5.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Battery mode and then to Online mode in
approximately ten
seconds.
The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM
status indicates
ONLINE.
NOTE
•
•
The Variable Module Management System mode commands are displayed only if enabled at the factory or by an
Eaton Customer Service Engineer.
The Variable Module Management System and Energy Saver System modes are mutually exclusive. If the Energy
Saver System mode is enabled, the Variable Module Management System mode commands will not be displayed.
NOTE
•
•
The Variable Module Management System mode commands are displayed only if enabled at the factory or by an
Eaton Customer Service Engineer.
The Variable Module Management System and Energy Saver System modes are mutually exclusive. If the Energy
Saver System mode is enabled, the Variable Module Management System mode commands will not be displayed.